Motor potentiometer MOP down
Bit15
CDS Bit 0 (Local/Remote-Hand/Auto) 0
r0968
Status word 1
Displays active status word of VSD (in binary) and can be used to diagnose which commands
are active.
Unit: -
Min: -
Bit fields:
Bit00
VSD ready
Bit01
VSD ready to run
Bit02
VSD running
Bit03
VSD fault active
Bit04
OFF2 active
Bit05
OFF3 active
Bit06
ON inhibit active
Bit07
VSD warning active
Bit08
Deviation setp. / act. value
Bit09
PZD control
Bit10
Maximum frequency reached
Bit11
Warning: Motor current limit
Bit12
Motor holding brake active
Bit13
Motor overload
Bit14
Motor runs direction right
Bit15
VSD VSD overload
P0970
Factory reset
P0970=1 resets all parameters to their default values.
Unit: -
Min: 0
Settings:
0=Disabled
Dependency:
First set P0010=30 (factory settings).
Stop VSD (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
P0918 (CB address),
P2010 (USS baud rate) and
P2011 (USS address)
P0971
Transfer data from RAM to EEPROM
Transfers values from RAM to EEPROM when set to 1.
Unit: -
Min: 0
Settings:
0=Disabled
Note:
All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
P1000[2]
Selection of frequency setpoint
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is
selected from the least significant digit (i.e., 0 to 6) and any additional setpoint from the most
significant digit (i.e., x0 through x6).
Unit: -
Min: 0
Data:
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least
significant digit (i.e., 0 to 6) and any additional setpoint from the most significant digit (i.e., x0 through x6).
Example:
Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor potentiometer.
Settings:
0=No main setpoint
1= Motor potentiometer (MOP) setpoint
2=Analog setpoint
3=Fixed frequency
4=USS on BOP link
5=USS on COM link
6= Communication board (CB) on COM link
7=Analog setpoint 2
10=No main setpoint + MOP setpoint
11=MOP setpoint + MOP setpoint
12=Analog setpoint + MOP setpoint
13=Fixed frequency + MOP setpoint
14=USS on BOP link + MOP setpoint
15=USS on COM link + MOP setpoint
16=CB on COM link + MOP setpoint
17=Analog setpoint 2 + MOP setpoint
20=No main setpoint + Analog setpoint
21=MOP setpoint + Analog setpoint
22=Analog setpoint + Analog setpoint
23=Fixed frequency + Analog setpoint
24=USS on BOP link + Analog setpoint
25=USS on COM link + Analog setpoint
26=CB on COM link + Analog setpoint
27=Analog setpoint 2 + Analog setpoint
30=No main setpoint + Fixed frequency
31=MOP setpoint + Fixed frequency
32=Analog setpoint + Fixed frequency
33=Fixed frequency + Fixed frequency
34=USS on BOP link + Fixed frequency
35=USS on COM link + Fixed frequency
Siemens
Building Technologies
Def: -
Def: 0
Def: 0
Def: 2
Commissioning Guide
10 Parameterization
0
NO, 1
YES
NO, 1
YES
Max: -
0
NO, 1
0
NO, 1
0
NO, 1
0
NO, 1
0
YES, 1
0
YES, 1
0
NO, 1
0
NO, 1
0
YES, 1
0
NO, 1
0
NO, 1
0
YES, 1
0
NO, 1
0
YES, 1
0
NO, 1
0
YES, 1
Max: 1
1=Parameter reset
Max: 1
1=Start transfer
Max: 77
40=No main setpoint + USS on BOP link
41=MOP setpoint + USS on BOP link
42=Analog setpoint + USS on BOP link
43=Fixed frequency + USS on BOP link
44=USS on BOP link + USS on BOP link
45=USS on COM link + USS on BOP link
46=CB on COM link + USS on BOP link
47=Analog setpoint 2 + USS on BOP link
50=No main setpoint + USS on COM link
51=MOP setpoint + USS on COM link
52=Analog setpoint + USS on COM link
53=Fixed frequency + USS on COM link
54=USS on BOP link + USS on COM link
55=USS on COM link + USS on COM link
56=CB on COM link + USS on COM link
57=Analog setpoint 2 + USS on COM link
60=No main setpoint + CB on COM link
61=MOP setpoint + CB on COM link
62=Analog setpoint + CB on COM link
63=Fixed frequency + CB on COM link
64=USS on BOP link + CB on COM link
65=USS on COM link + CB on COM link
66=CB on COM link + CB on COM link
67=Analog setpoint 2 + CB on COM link
70=No main setpoint + Analog setpoint 2
71=MOP setpoint + Analog setpoint 2
72=Analog setpoint + Analog setpoint 2
73=Fixed frequency + Analog setpoint 2
74=USS on BOP link + Analog setpoint 2
75=USS on COM link + Analog setpoint 2
Level 3
YES
YES
YES
YES
NO
NO
YES
YES
NO
YES
YES
NO
YES
NO
YES
NO
Level 1
Level 3
Level 1
77 / 100
CM1G5192en
29.07.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents