7.6.1 Parameter changes

Start with quick commissioning according to application 1
Par. no.
Value
Parameter function
P0003
3
User access level
P0701(0)
16
Function of digital input 1
in "Auto" mode
P0702(0)
16
Function of digital input 2
in "Auto" mode
P0703(0)
29
Function of digital input 3
in "Auto" mode
P0703(1)
29
Function digital input 3
in "Hand" mode
P0756(1)
1
Analog input
P0757(1)
0
Scaling of analog input 2: x1
P0758(1)
0
Scaling of analog input 2: y1
P0759(1)
10
Scaling of analog input 2: x2
P0760(1)
100
Scaling of analog input 2: y2
P2201
80%
Fixed setpoint of digital input 1
P2202
20%
Fixed setpoint of digital input 2
P2253(0)
2224
PID setpoint
P2306
1
PID acting direction
P2200(0)
1
Enable PID controller
P2280
10
PID proportional gain
P2285
30 s
PID integral action time
r2262
Current setpoint
r2272
Actual value
50 / 100
Siemens
Building Technologies
Commissioning Guide
7 Applications
Function selection
Expert access
Fixed setpoint + ON
Fixed setpoint + ON
In the event of an external alarm, fan will be stopped
In the event of an external alarm, fan will be stopped
DC...10 V (default)
(Default)
(Default)
(Default)
(Default)
Fixed
Indirect
PID controller enabled
CM1G5192en
29.07.2010