Par. no.
Value
Parameter function
P0760(1)
100
Scaling of analog input 2: y2
P2201
50%
Setpoint CO
P2203
-50%
Setpoint for digital input 3
P2253(0)
2224
PID setpoint
P2306
0
PID acting direction
P2200(0)
1
Enable PID controller
P2280
0.5
PID proportional gain
P2285
60 s
PID integral action time
r2262
Current filtered PID setpoint
r2272
Actual value
7.6 Application 6
Ventilation equipment shall be controlled with the help of the integrated PID controller.
Switching on / off via 2 digital inputs (application matched for 2 different setpoints via central control unit
RWI65.02, load-dependent fan control)
External alarm via digital input 3; in the event of an alarm, fan will be stopped
Error message via relay output 1
Indication of operation via relay output 2
L1
L2
L3
PE
Fuses
L1
L2
L3
20
21
22
23
24
25
SED2
P(1)
5
6
Hz
I
Hand
Fn
7
9
0
Auto
P
10
2
SED2
u
v
w
M
3
Siemens
Building Technologies
2
Error
Relay 1
Com
Run
Relay 2
Com
Inspection switch
Fan
Commissioning Guide
7 Applications
Function selection
(Default)
Fixed
Direct
PID controller enabled
- On: Speed high
- On: Speed low
- External alarm
Building Management System
(BMS)
DIP switch setting
ON
■ ■
OFF
1
2
5192A06en
1 = Analog input 1
OFF = DC 0...10 V
ON = 0...20 mA
2 = Analog input 2
OFF = DC 0...10 V
ON = 0...20 mA
49 / 100
CM1G5192en
29.07.2010