P2212
P2213
P2214
P2215
Dependency:
P2000=1 required at user access level 2 to enable the setpoint source
In mode 1 (above):
In mode 2 (above): If inputs programmed to PID fixed setpoint and selected together, the selected setpoints are summed.
Note:
You may mix different types of frequencies. However, remember that they will be summed if selected together.
P2201=100% corresponds to 4000 hex.
Default fixed PID setpoint values are as follows:
Fixed PID
1
2
3
4
5
P2216,
Fixed PID setpoint mode - Bit 0, Bit 1, Bit 2, and Bit 3
P2217,
P2218, P2219
Fixed frequencies for PID setpoint can be selected in 3 different modes. Parameter P1016
defines the mode of selection bit 0.
Unit: -
Min: 1
Settings:
1=Direct selection
P2220[2]
BI: Fixed PID setpoint select Bit 0
Defines command source of fixed PID setpoint selection bit 0.
Unit: -
Min: 0:0
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P2220[0]: VSD in "Auto" mode
P2221[2].
BI: Fixed PID setpoint select Bit 1, Bit 2, and Bit 3
P2222[2],
P2223[2]
Defines command source of fixed PID setpoint selection bit 1.
Unit: -
Min: 0:0
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
Index:
For P2221:
P2221[0]: VSD in "Auto" mode
P2221[1]: VSD in "Hand" mode
r2224
CO: Act. fixed PID setpoint
Displays total output of PID fixed setpoint selection
Unit: % Min: -
Note:
r2224=100% corresponds to 4000 hex
P2225, P2227
Fixed PID setpoint mode – Bit 4 and Bit 5
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Unit: -
Min: 1
Settings:
1=Direct selection
P2226[2]-
BI: Fixed PID setpoint select Bit 4 and Bit 5
P2228[2]
P2226[2]
Min: 0:0
P2227
Min: 1
P2228[2]
Min: 0
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
Index:
For P2226:
P2226[0]: VSD in "Auto" mode
P2226[1]: VSD in "Hand" mode
Siemens
Building Technologies
FF12
Active
FF13
Active
FF14
Active
FF15
Active
ON command required to start motor (enable pulses).
Default
Fixed PID
0.00
6
10.00
7
20.00
8
30.00
9
40.00
10
Def: 1
2=Direct selection + ON command
Def: 0:0
Def: 0:0 (P2223[2]:722.3
For P2222:
P2222[0]: VSD in "Auto" mode
P2222[1]: VSD in "Hand" mode
Def: -
Def: 1
2=Direct selection + ON command
Def: 722:4
Def: 1
Def: 722:5
Commissioning Guide
10 Parameterization
Active
Inactive
Active
Inactive
Active
Active
Active
Active
Default
Fixed PID
50.00
11
60.00
12
70.00
13
80.00
14
90.00
15
Max: 3
3=Binary coded selection + ON command
Max: 4000:0
P2220[1]: VSD in "Hand" mode
Max: 4000:0
For P2223:
P2223[0]: VSD in "Auto" mode
P2223[1]: VSD in "Hand" mode
Max: -
Max: 2
3=Binary coded selection + ON command
Max: 4000:0
Max: 2
Max: 4000:0
For P2228:
P2228[0]: VSD in "Auto" mode
P2228[1]: VSD in "Hand" mode
Inactive
Active
Active
Active
Default
100.00
110.00
120.00
130.00
130.00
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
89 / 100