Siemens SED2 Commissioning Manual page 73

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

P0718
CO/BO: Hand / Auto
Mode after startup.
Unit: -
Min: 0
Settings:
0=Auto
r0722
CO/BO: Binary input values
Displays status of digital inputs.
Unit: -
Min: -
Bit fields:
Bit00
Digital input 1
Bit01
Digital input 2
Bit02
Digital input 3
Bit03
Digital input 4
Bit04
Digital input 5
Bit05
Digital input 6
Bit06
Digital input 7 (via ADC 1)
Bit07
Digital input 8 (via ADC 2)
Note:
Segment is lit when signal is active.
P0725
PNP / NPN digital inputs
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs
simultaneously.
Unit: -
Min: 0
Settings:
0=NPN mode ==> low active
P0731[2]
BI: Function of digital output 1
Defines source of digital output 1.
Unit: -
Min: 0.0
Settings:
52.0
VSD ready
52.1
VSD ready to run
52.2
VSD running
52.3
VSD fault active
52.4
OFF2 active
52.5
OFF3 active
52.6
Switch on inhibit active
52.7
VSD warning active
52.8
Deviation setpoint/actual value
52.9
PZD control (Process Data Control) 0 Closed
52.A
Maximum frequency reached
52.B
Warning: Motor current limit
52.C
Motor holding brake (MHB) active
52.D
Motor overload
Index:
P0731[0]: VSD in "Auto" mode
P0732[2]
BI: Function of digital output 2
Defines source of digital output 2.
Unit: -
Min: 0.0
Details:
See P0731 (function of digital output 1).
r0747
CO/BO: State of digital outputs
Displays state of digital outputs (also includes inversion of digital outputs via P0748).
Unit: -
Min: -
Bit fields:
Bit00
Digital output 1 energized
Bit01
Digital output 2 energized
Dependency:
Bit 0=Relay deenergized / contacts open
Bit 1=Relay energized / contacts closed
P0748
Invert digital outputs
Defines high and low states of relay for a given function.
Unit: -
Min: 0
Bit fields:
Bit00
Invert digital output 1
Bit01
Invert digital output 2
r0752[2]
Act. input of ADC [V] or [mA]
Displays smoothed analog input value in Volts before the characteristic block.
Unit: -
Min: -
Index:
r0752[0]: Analog input 1 (ADC 1)
P0753[2]
Smooth time ADC
Defines filter time (PT1 filter) in [ms] for analog input.
Unit: ms
Min: 0
Index:
P0753[0]: Analog input 1 (ADC 1)
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
r0754[2]
Act. ADC value after scaling [%]
Shows smoothed value of analog input in [%] after scaling block.
Unit: % Min: -
Index:
r0754[0]: Analog input 1 (ADC 1)
Dependency:
P0757 to P0760 define range (ADC scaling)
Siemens
Building Technologies
Def: 0
Def: -
Def: 1
Def: 52.3
0 Closed
0 Closed
0 Closed
0 Closed
1 Closed
1 Closed
0 Closed
0 Closed
1 Closed
0 Closed
1 Closed
0 Closed
1 Closed
Def: 52.2
Def: -
Def: 0
0
0
Def: -
Def: 100
Def: -
Commissioning Guide
10 Parameterization
Max: 1
1=Hand
Max: -
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
0
OFF, 1
ON
Max: 1
1=PNP mode ==> high active
Max: 4000.0
52.E
Motor running direction right
52.F
VSD overload
53.0
DC brake active
53.1
VSD frequency less switch off limit
53.2
VSD frequency less minimum freq. 0 Closed
53.3
Current greater or equal than limit
53.4
Act. freq. greater comparison freq.
53.5
Act. freq. less comparison freq.
53.6
Act. freq. greater/equal setpoint
53.7
Voltage less than threshold
53.8
Voltage greater than threshold
53.A
PID output at lower limit (P2292)
53.B
PID output at upper limit (P2291)
P0731[1]: VSD in "Hand" mode
Max: 4000.0
Max: -
0
NO, 1
YES
0
NO, 1
YES
Max: 7
NO, 1
YES
NO, 1
YES
Max: -
r0752[1]: Analog input 2 (ADC 2)
Max: 10000
P0753[1]: Analog input 2 (ADC
Max: -
r0754[1]: Analog input 2 (ADC 2)
Level 3
Level 3
Level 3
Level 2
0 Closed
1 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
0 Closed
Level 2
Level 3
Level 3
Level 2
Level 3
Level 2
73 / 100