Error
Cause
F0221
PID feedback below minimum value of P2268
PID feedback
below min.
value
F0222
PID feedback above maximum value of P2267
PID feedback
above max.
value
F0450
VSD self-test failed. Cause can be found based
on error value in parameter r0949:
BIST tests
r0949 = 1
failure
r0949 = 2
r0949 = 4
r0949 = 8
r0949 = 16 Error of internal RAM test when
F0452
Belt failure detection without sensor (refer to
section 8.1)
Belt failure
detected
Belt faulty
Belt failure detection with sensor (refer to
section 8.2)

9.2 Warning code list

Error
Cause
A0501
See F0001
Current limit
A0502
See F0002
Overvoltage limit
A0503
See F0003
Undervoltage limit
A0504
See F0004
VSD over-
temperature
A0505
See F0005
2
VSD I
t
Siemens
Building Technologies
Tests on power section failed
Tests on control section failed
Function tests failed
Tests on I/O module failed
switching on
Commissioning Guide
9 Display messages
Diagnostics and troubleshooting
− Check settings of the VSD's PID control loop
− Change the value of P2268
− A reset to the default values cancels all undesired
parameter settings and retrieves the default settings.
The VSD must be recommissioned
− Check the settings of the VSD's PID control loop
− Change the value of P2267
− A reset to the default values cancels all undesired
parameter settings and retrieves the default settings.
The VSD must be recommissioned
− Switch the VSD off and on again
− A reset to the default values cancels all undesired
parameter settings and retrieves the default settings.
The VSD must be recommissioned
− If the fault cannot be rectified by making a reset to
the default settings, the VSD must be replaced
− Check the settings of the following parameters and
compare them with the torques currently measured
via parameter r0031:
P2182 (frequency theshold f1)
P2183 (frequency theshold f2)
P2184 (frequency theshold f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3)
P2190 (lower torque threshold 3)
P2192 (time delay load torque supervision)
− Tolerance bands of more than 50% must be set,
depending on the type of application
Check position and strength of the belt
− Check to ensure that the sensor is correctly
connected to digital input # 5
− Check settings of the following parameters:
− P0400 type of sensor
− P0409 (pulses / s at rated speed)
− P2181 (triggering conditions)
− P2191 (speed supervision tolerance)
− P2192 (time delay for P2191)