Siemens SED2 Commissioning Manual page 72

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

2
P0610
Motor I
t temperature reaction
Defines reaction when motor temperature reaches warning threshold.
Unit: -
Min: 0
Settings:
0=No reaction, warning only
P0640
Motor overload factor [%]
Defines reaction when motor temperature reaches warning threshold.
Unit: % Min: 10.0
Dependency:
Limited to maximum VSD current or to 400% of rated motor current (P0305), whichever is lower.
P0700[2]
Selection of command source
Selects digital command source.
Unit: -
Min: 0
Settings:
0=Factory default setting
1=BOP (keypad)
Index:
P0700[0]: VSD in "Auto" mode
Note:
Changing this parameter resets (to default) all settings on item selected. For example: Changing form 1 to 2 resets all
digital inputs to default settings.
P0701[2]
Function of digital input 1
Selects function of digital input 1.
Unit: -
Min: 0
Settings:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 – coast to standstill
4=OFF3 – quick ramp-down
9=Fault acknowledge
10=JOG right
Index:
P0701[0]: VSD in "Auto" mode
Dependency:
Setting 99 (enable BICO parameterization) requires P0700 (command source) or P3900 (end of quick
commissioning)=1, 2 or P0970 (factory reset)=1 in order to reset.
Note:
Setting 99 (BICO) for expert use only.
P0702[2]
Function of digital input 2
Selects function of digital input 2.
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1).
P0703[2]
Function of digital input 3
Selects function of digital input 3.
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1).
P0704[2]
Function of digital input 4
Selects function of digital input 4.
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1).
P0705[2]
Function of digital input 5
Selects function of digital input 5 (via analog input).
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1).
Note:
Setting 17 is not supported.
P0706[2]
Function of digital input 6
Selects function of digital input 6 (via analog input).
Unit: -
Min: 0
Detail:
See P0701 (function of digital input1).
Note:
Setting 17 is not supported.
P0707[2]
Function of digital input 7
Selects function of digital input 7 (via analog input).
Unit: -
Min: 0
Settings:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 – coast to standstill
4=OFF3 – quick ramp-down
9=Fault acknowledge
Index:
P0707[0]: VSD in "Auto" mode
Dependency:
Signals about 4 V are active, signals below 1.6 V are inactive.
Note:
Signals above 4 V are active, signals below 1.6 V are inactive.
P0708[2]
Function of digital input 8
Selects function of digital input 8 (via analog input).
Unit: -
Min: 0
Detail:
See P0707 (function of digital input7).
72 / 100
Siemens
Building Technologies
Def: 2
1=Warning and Imax reduction
(results in reduced output freq.)
Def: 110.0
Def: 2
2=Terminal
4=USS on BOP link
Def: 1
11=JOG left
12=Reverse
13=MOP up (increase freq.)
14=MOP down (decrease freq.)
15=Fixed setpoint (direct selection)
16=Fixed setpoint (direct selection + ON)
17=Fixed setpoint (binary coded selection+ON)
Def: 12
Def: 9
Def: 15
Def: 15
Def: 15
Def: 0
10=JOG right
11=JOG left
12=Reverse
13=MOP up (increase freq.)
14=MOP down (decrease freq.)
Def: 0
Commissioning Guide
10 Parameterization
Max: 2
2=Warning and trip F0011
Max: 400.0
Max: 6
5=USS on COM link
6=CB on COM link
P0700[1]: VSD in "Hand" mode
Max: 99
25=DC brake enable
26=Enable essential service
27=Enable PID
28=Bypass mode command input
29=External trip
33=Disable additional freq setpoint
99=Enable BICO parameterization
P0701[1]: VSD in "Hand" mode
Max: 99
Max: 99
Max: 99
Max: 99
Max: 99
Max: 99
25=DC brake enable
26=Enable essential service
29=External trip
33=Disable additional freq. setpoint
99=Enable BICO parameterization
P0707[1]: VSD in "Hand" mode
Max: 99
Level 3
Level 3
Level 1
Level 2
Level 2
Level 2
Level 2
Level 2
Level 2
Level 3
Level 3
CM1G5192en
29.07.2010