SED2 Variable Speed Drive
Application Guide «Fire Mode»
CM1A5192en_01
23.10.2007
Air handling
system
P
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SED2

  • Page 1 Air handling system ∆ Escape and emergency route ∆ SED2 Variable Speed Drive Application Guide «Fire Mode» CM1A5192en_01 23.10.2007 Building Technologies...
  • Page 2 Siemens Switzerland Ltd. Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 © 2007 Siemens Switzerland Ltd. www.siemens.com/sbt Subject to change 2 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies 23.10.2007...
  • Page 3: Table Of Contents

    Smoke and heat extraction in the building..........10 Guidelines and standards for smoke and heat extraction.......10 Interplay of ventilation plant and smoke and heat extraction in the event of fire... 11 Operation of SED2 in the event of fire ............12 Application Examples................14 Application Example 1 ................14 4.1.1...
  • Page 4 Automatic re-start in ESM/Fire Mode ............40 6.6.5 Acknowledging a fault when ESM/Fire Mode is first enabled ....41 Advanced settings...................41 6.7.1 ESM/Fire Mode Control Words for the SED2 .........41 6.7.2 Starting the SED2 in ESM/Fire Mode............42 6.7.3 Stopping the SED2 in ESM/Fire Mode............42...
  • Page 5: About This Document

    Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance These documents have been prepared with great care.
  • Page 6: Document Use/Request To The Reader

    Swiss headquar- ters. E-mail: fieldsupport-zug.ch.sbt@siemens.com. Please note that without prejudice to your statutory rights, Siemens accepts no li- ability for any losses resulting from non-observance or improper observance of the points referred to above.
  • Page 7: Safety And Ce Compliance

    • When using the analog inputs, the DIP switches must be correctly set and the analog inputs correctly configured before enabling them. If this is not done, the motor may start inadvertently 7 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Safety and CE compliance 23.10.2007...
  • Page 8: Exclusion Of Liability

    For these reasons, Siemens Building Technologies assumes no responsibility for any faults, malfunctions and damage of the SED2 itself or of any other types of components used in the relevant HVAC plant, or for direct or indirect damage re- sulting from activation of fire/emergency operation.
  • Page 9: Qualified Personnel

    User group These Guidelines were drawn-up to support customers and employees of Siemens AG when engineering plants and machines. The functions and features described in this document refer only to the SED2 Vari- able Speed Drive with version Firmware 1.40 or greater.
  • Page 10: Introduction

    AS/NZS 1668.1:1998 New Zealand The use of ventilation and airconditioning in buildings - Fire and smoke control in multi-compartment buildings Switzerland prSWKI BT101 Teil 1-6 Rauch- und Wärmefreihaltung 10 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Introduction 23.10.2007...
  • Page 11: Interplay Of Ventilation Plant And Smoke And Heat Extraction In The Event Of Fire

    Functioning principle of smoke and heat extraction and ventilation plant in the event of fire: Escape and Air handling emergency route system ∆ ∆ 11 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Introduction 23.10.2007...
  • Page 12: Operation Of Sed2 In The Event Of Fire

    Regional Companies (RC). This means that V1.40 in- cludes all findings made thus far so that the SED2 also represents state of the art as far as ESM is concerned.
  • Page 13 • In normal operation, the Desigo system delivers the switch-on command and setpoint to the VSD via bus • If the fire alarm center activates ESM, the SED2 will start to operate with the maximum speed at 50 Hz and suppresses the protective functions and error messages as described above •...
  • Page 14: Application Examples

    • In normal operation the SED2 is receiving the setpoint over the analogue input 1, e.g. from a BAC, e.g. DESIGO PX. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and the setpoint is still coming over the analogue input.
  • Page 15: Parameter Setting

    • The information “drive fault” and “drive running” is still available on the 2 relay outputs. On demand the information “ESM active” can be configured to a relay output. 15 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 16: Application Example 2

    • In normal operation the SED2 is receiving the setpoint over the analogue input 1 e.g. from a BAC e.g. DESIGO PX. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and to a fixed frequency e.g. 40Hz.
  • Page 17: Parameter Setting

    • The information “drive fault” and “drive running” is still available on the 2 relay outputs. On demand the information “ESM active” can be configured to a relay output. 17 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 18: Application Example 3

    • In normal operation the SED2 is controlled from the Desigo PX via bus commu- nication using the PTE module. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and the setpoint is still coming from the Desigo over the bus.
  • Page 19: Parameter Setting

    • The fault F0072 (bus communication failure) will be ignored whilst ESM is active. • In this example a DESIGO PX is used as the communication master but any communication (FLN, P1, N2) could be used just as effectively. 19 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 20: Application Example 4

    • In normal operation the SED2 is controlled from the Desigo PX via bus commu- nication using the PTE module. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and to a fixed frequency e.g. 40Hz.
  • Page 21: Parameter Setting

    • The fault F0072 (bus communication failure) will be ignored whilst ESM is active. • In this example a DESIGO PX is used as the communication master but any communication (FLN, P1, N2) could be used just as effectively. 21 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 22: Application Example 5

    This application is equivalent to application 4 in the Commissioning Guide CM1G5192 just enhanced with the ESM function. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and the internal PID loop keeps on working.
  • Page 23: Parameter Setting

    • The information “drive fault” and “drive running” is still available on the 2 relay outputs. On demand the information “ESM active” can be configured to a relay output. 23 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 24: Application Example 6

    This application is equivalent to application 4 in the Commissioning Guide CM1G5192 just enhanced with the ESM function. • In case of fire the fire control panel signals this to the SED2, it is going in the ESM mode and to a fixed frequency e.g. 40Hz.
  • Page 25: Parameter Setting

    • The information “drive fault” and “drive running” is still available on the 2 relay outputs. On demand the information “ESM active” can be configured to a relay output. 25 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Application Examples 23.10.2007...
  • Page 26: Commissioning Wizard For Essential Service Mode

    Commissioning Wizard for Essential Service Mode Introduction Up to now the SED2 drives have been commissioned over the BOP/AOP respec- tively over EasyComm which is a parameterisation and monitoring tool for the SED2 family. This may be inefficient particularly with more complex applications such as ESM and bigger projects.
  • Page 27: Parameterisation Of Esm Function

    Following windows will show up, to make life as easy as possible: Note If the user clicks «No» it will take him back to the start. 27 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Commissioning Wizard for Essential Service Mode 23.10.2007...
  • Page 28 28 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Commissioning Wizard for Essential Service Mode 23.10.2007...
  • Page 29: Languages

    If the EasyComm language is set to English the Commissioning Wizard windows and the description respectively help files will automatically appear in English. Distribution The SED2 Commissioning Wizard is available from you local sales representative free of charge. An automatic installer makes the installation of the Commissioning Wizard easy.
  • Page 30: Essential Service Mode (In-Depth Information)

    Essential Service Mode (in-depth in- formation) • With V1.40 and higher, all SED2 errors and warnings will be ignored, the excep- tion being hard errors, such as F0001, F0002, F0003, F0022 and F0023. These hard errors can not be ignored since they could lead to the destruction of the VSD.
  • Page 31: Assigning The Esm Function To A Din (Digital Input)

    ESM control word is activated Once P1271 has been activated, the ESM control word will take priority once the DIN assigned to ESM/Fire Mode is enabled. 31 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Essential Service Mode (in-depth information)
  • Page 32: Defining The Main Speed (Frequency) Setpoint For Esm

    P1000 in000 from what is set during Quick Commissioning. If the SED2 in Standard mode is controlled by a 0-10Vdc signal via AIN1 and the Example same method of speed control is required when ESM is activated, then:...
  • Page 33: Disabling The Additional Setpoint

    ESM setpoint is via a Fixed Frequency. (See also next section on “disabling the Additional Setpoint”) P1000 in000 = 23 The standard setpoint controlling the SED2 is via a LON system (optional LON Example 2 module needs to be connected).
  • Page 34 Required: P1000 in000= x3 (x =standard setpoint) Display of P1271 in001 (ESM Control word 2) on the BOP Alternatively, use EasyComm to set the correct bit. 34 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Essential Service Mode (in-depth information)
  • Page 35: Reverse Direction In Esm/Fire Mode

    Alternatively, use EasyComm to set the correct bit. Example 1 If a digital input is set to reverse (e.g. DI4 to 12) and in addition the ESM is set to reverse the behaviour of the SED2 is as follows: DIN2 DIN4...
  • Page 36 Example 2 If you use DIN1 as ON/OFF1 (setting 1 = default) and DIN2 as ON reverse/OFF1 (setting 2) and in addition the ESM is set to reverse the behaviour of the SED2 is as follows: DIN1 DIN4 DIN2 Motor Direction...
  • Page 37: Pid Control In Esm/Fire Mode

    Configure PID related parameters P2201~P23xx accordingly to application Display of P1271 in001 (ESM Control word 2) on the BOP Alternatively, use EasyComm to set the correct bit. 37 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Essential Service Mode (in-depth information)
  • Page 38: Pid Control In Standard Mode But Disabled In Esm/Fire Mode

    Configure PID related parameters P2201~P23xx accordingly to application Display of P1271 in001 (ESM Control word 2) on the BOP Alternatively, use EasyComm to set the correct bit. 38 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Essential Service Mode (in-depth information)
  • Page 39: Pid Control In Esm/Fire Mode But Disabled In Standard Mode

    Alternatively, use EasyComm to set the correct bit. 6.5.4 PID Control disabled in ESM/Fire Mode and Standard mode Leave P2200 at factory default (0.0) and leave P1271 in000 bit08 inactive. 39 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies Essential Service Mode (in-depth information) 23.10.2007...
  • Page 40: Indication Of Esm/Fire Mode

    F0002/F0003: Overvoltage and undervoltage conditions will cause the drive to trip F0023: The disconnection of the motor while the SED2 is running In the event any of these faults occur, the SED2 will shut down with an OFF2 stop (coast to stop) and attempt a fault acknowledge and automatic restart.
  • Page 41: Acknowledging A Fault When Esm/Fire Mode Is First Enabled

    SED2 will acknowledge, restart and ignore all ‘soft faults’ and attempt to acknowl- edge and restart any ‘hard faults’. If a hard fault is still present, then the SED2 will trip and attempt again indefinitely or until the SED2 is destroyed.
  • Page 42: Starting The Sed2 In Esm/Fire Mode

    6.7.2 Starting the SED2 in ESM/Fire Mode Enabling ESM will ALWAYS RUN the SED2, even if there is no RUN command ac- tivated in the standard settings. Once ESM/Fire Mode has been enabled, the display on the BOP will flash Example: within a building the Air Handling Units may be stopped at night-time or weekend.
  • Page 43 43 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies 23.10.2007...
  • Page 44 Siemens Switzerland Ltd. Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 © 2007 Siemens Switzerland Ltd. www.siemens.com/sbt Subject to change 44 / 44 Siemens Application Guide «Fire Mode» CM1A5192en_01 Building Technologies 23.10.2007...