Siemens SED2 Commissioning Manual page 69

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Unit: -
Min: -
Bit fields:
Bit00
Fixed frequency Bit 0
Bit01
Fixed frequency Bit 1
Bit02
Fixed frequency Bit 2
Bit03
Fixed frequency Bit 3
Bit08
PID enabled
Bit09
DC brake enabled
Bit11
Droop
Bit12
Not used
Bit13
External fault 1
r0056
CO/BO: Status of motor control
Displays status of motor control (V/f status), which can be used to diagnose VSD status.
Unit: -
Min: -
Bit fields:
Bit00
Init. control finished
Bit01
Motor demagnetizing finished
Bit02
Pulses enabled
Bit03
Voltage soft start select
Bit04
Motor excitation finished
Bit05
Starting boost active
Bit06
Acceleration boost active
Bit07
Frequency is negative
Bit08
Field weakening active
Bit09
Volts setpoint limited
Bit10
Slip frequency limited
Bit11
F_out > F_max
Bit12
Phase reversal selected
Bit13
I-max controller active
Bit14
Vdc-max controller active
Bit15
Vdc-min controller active
r0061
CO: Act. rotor speed
Displays current speed detected by encoder.
Unit: Hz
Min: -
r0086
CO: Act. active current
Displays active (real part) of motor current.
Unit: A Min: -
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
P0100
Europe / North America
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in
[kW] or [hp].
The default settings for the nominal rating plate frequency (P0310) and maximum motor
frequency (P1082) are also set automatically here, in addition to reference frequency (P2000).
Unit: -
Min: 0
Settings:
0=Europe [kW], frequency default 50 Hz
1=North America [hp], frequency default 60 Hz
2=North America [kW], frequency default 60 Hz
Dependency:
The setting of DIP switch 2 under the I/O module determines the validity of settings 0 and 1 for P0100 according to the
following table:
DIP 2 Setting
Off
On
Stop VSD first (i.e. disable all pulses) before you change this parameter.
P0010=1 (commissioning mode) enables changes to be made.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (see P0340 - calculation of motor parameters).
Note:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table above.)
r0200
Act. power stack code number
Identifies hardware variant.
Unit: -
Min: -
Note:
Parameter r0200=0 indicates that no power stack has been identified.
r0206
Rated VSD power [kW] / [hp]
Displays nominal rated motor power from the VSD.
Unit: -
Min: -
Dependency:
Value is displayed in [kW] or [hp], depending on setting for P0100 (operation for Europe / North America).
r0207
Nominal motor current
Displays maximum continuous output current of the VSD.
Unit: A Min: -
r0208
Rated VSD voltage
Displays nominal AC supply voltage of the VSD.
Unit: V
Min: -
Value:
r0208=230 : 200 - 240 V +/- 10%
Siemens
Building Technologies
Def: -
Def: -
Freq. limited
Def: -
Def: -
Def: 0
Meaning
[kW], frequency default 50 [Hz]
[hp], frequency default 60 [Hz]
Def: -
Def: -
Def: -
Def: -
r0208=400 : 380 - 480 V +/- 10%
Commissioning Guide
10 Parameterization
Max: -
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
YES, 0
NO
Max: -
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
0
NO, 1
YES
Max: -
Max: -
Max: 2
P0100 Setting
Overwrites
1
Overwrites
0
Max: -
Max: -
Max: -
Max: -
Level 3
Level 3
Level 3
Level 1
Meaning
[hp], frequency default 60 [Hz]
[kW], frequency default 50 [Hz]
Level 3
Level 3
Level 3
Level 3
r0208=575 : 500 - 600 V +/- 10%
CM1G5192en
29.07.2010
69 / 100