Siemens SED2 Commissioning Manual page 90

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

P2231
Setpoint memory of PID-MOP
Setpoint memory
Unit: -
Min: 0
Settings:
0=PID-MOP setpoint will not be stored
Dependency:
If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command.
If 1 is selected, active setpoint is 'remembered' and P2240 updated with current value.
Note:
See P2240 (setpoint of PID-MOP).
P2232
Inhibit rev. direct. of PID-MOP
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main
setpoint of additional setpoint (using P1000).
Unit: -
Min: 0
Settings:
0=Reverse direction is allowed
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase / decrease frequency
either by using digital inputs or motor potentiometer up / down buttons.
P2240[2]
Setpoint of PID-MOP
Setpoint of the motor potentiometer. Allows user to set a digital PID setpoint in [%].
Unit: % Min: -200.00
Dependency:
To change the setpoint: 1. Use the up / down button on BOP or
Note:
P2240=100% corresponds to 4000 hex
r2250
CO: Output setpoint of PID-MOP
Displays output setpoint of motor potentiometer in [%].
Unit: % Min: -
Note:
r2250=100% corresponds to 4000 hex
P2253[2]
CI: PID setpoint
Defines setpoint source for PID setpoint input.
Unit: -
Min: 0:0
Details:
This parameter allows the user to select the source of the PID setpoint. Normally, a digital setpoint is selected either
using a fixed PID setpoint or an active setpoint.
Settings:
755=Analog input 1
Index;
P2253[0]: VSD in "Auto" mode
P2254[2]
CI: PID trim source
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the
PID setpoint.
Unit: -
Min: 0:0
Settings:
755=Analog input 1
Index;
P2254[0]: VSD in "Auto" mode
P2261
PID setpoint filter time constant
Sets a time constant for smoothing the PID setpoint.
Unit: s
Min: 0.00
Note:
0 = No smoothing
r2262
CO: Filtered PID setp. after RFG
Displays filtered PID setpoint after PID-RFG in [%]
Unit: % Min: -
Note:
r2262=100% corresponds to 4000 hex
P2264[2]
CI: PID feedback
Selects the source of the PID feedback signal.
Unit: -
Min: 0:0
Settings:
755=Analog input 1 setpoint
Index:
P2264[0]: VSD in "Auto" mode
Note:
When analog input is selected, offset and gain can be implemented using parameters P0756 to P0760.
P2265
PID feedback filter time constant
Defines time constant for PID feedback filter.
Unit: s
Min: 0.00
P2267
Max. value for PID feedback
Sets the upper limit for the value of the feedback signal in [%].
Unit: % Min: -200.00
Note:
P2267=100% corresponds to 4000 hex.
When PID is enabled (P2200=1) and the signal rises above this value, the VSD will trip with F0222.
P2268
Min. value for PID feedback
Sets lower limit for value of feedback signal in [%]
Unit: % Min: -200.00
Note:
P2268=100% corresponds to 4000 hex.
When PID is enabled (P2200=1) and the signal rises above this value, the VSD will trip with F0221.
P2269
Gain applied to PID feedback
Allows the user to scale the PID feedback as a percentage value [%].
A gain of 100% means that the feedback signal has not changed from its default value.
Unit: -
Min: 0.00
90 / 100
Siemens
Building Technologies
Def: 1
Def: 1
Def: 10.00
2. Set P0702/P0703=13/14 (function of digital inputs 2 and 3)
Def: -
Def: 2250:0
2224=Fixed PI setpoint (see P2201 to P2207)
Def: 0:0
2224=Fixed PI setpoint (see P2201 to P2207)
Def: 0.00
Def: -
Def: 755:1
2224=Fixed PID setpoint
Def: 0.00
Def: 100.00
Def: 0.00
Def: 100.00
Commissioning Guide
10 Parameterization
Max: 1
1=PID-MOP setpoint will be stored (P2240 is updated)
Max: 1
1=Reverse direction inhibited
Max: 200.00
Max: -
Max: 4000:0
2250=Active PI setpoint (see P2240)
P2253[1]: VSD in "Hand" mode
Max: 4000:0
2250=Active PI setpoint (see P2240)
P2254[1]: VSD in "Hand" mode
Max: 60.00
Max: -
Max: 4000:0
2250=Output setpoint of PID-MOP
P2264[1]: VSD in "Hand" mode
Max: 60.00
Max: 200.00
Max: 200.00
Max: 500.00
Level 3
Level 3
Level 3
Level 3
Level 2
Level 3
Level 3
Level 3
Level 2
Level 3
Level 3
Level 3
Level 3