Application 7; Application 8 - Siemens SED2 Commissioning Manual

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Par. no.
Value
Parameter function
P2253(0)
2224
PID setpoint
P2264(0)
755.0
PID feedback
P2274
0 s
PID derivative action time
P2280
5
PID proportional gain
P2285
20 s
PID integral action time
P2306
0
PID acting direction
P2390
35%
Hibernation frequency
P2391
90 s
Hibernation timer
P2392
-2%
Restart PID controller deviation
r2262
Filtered PID setpoint
r2272
PID scaled feedback
r2273
PID error
r2294
PID output

7.8 Application 8

Condenser tower shall be controlled with the help of the integrated PID controller.
ON / OFF by LLSV relay interlock
QBE620 for pressure control
Indication of operation via relay output 2
L1
L2
L3
PE
Fuses
L1
L2
L3
20
21
22
23
24
25
SED2
P(1)
Hz
5
I
Hand
Fn
0
Auto
P
9
3
SED2
2
28
u
v
w
Inspection switch
M
3
Notes: When the chiller interlock latches, the VSD will start and maintain the pressure setpoint (P2201). If the
output of the VSD drops below the hibernation setpoint P2390, and the hibernation timer has elapsed
(P2391), the VSD will drop from the minimum motor frequency (P1080) to zero, and turn off. When the HP
exceeds the setpoint by 5% (P2392), the VSD will restart and ramp up to maintain the setpoint once more.
This feature allows the minimum motor frequency to be set to protect the motor from overheating and
stalling, while allowing the motor to turn off when not needed to prevent overcooling during the winter
months.
52 / 100
Siemens
Building Technologies
Error
Relay 1
Com
Run
Relay 2
Com
M
U
G
QBE620-P25
HP Sensor
Pump
Commissioning Guide
7 Applications
Function selection
PID setpoint source
Sets PID feedback source to AIN 1
Derivative action time
Proportional band
Integral action time
Direct acting loop
Hibernation setpoint [%]
Hibernation timer in seconds
Restart – PID error
Display actual setpoint in C
Display actual condenser temperature
Display actual PID error in %
Display actual VSD output in %
LLSV relay interlock
5192A08en
DIP switch setting
ON
1 = Analog input 1
■ ■
OFF
OFF = DC 0...10 V
1
2
ON = 0...20 mA
2 = Analog input 2
OFF = DC 0...10 V
ON = 0...20 mA
CM1G5192en
29.07.2010