Parameter Changes; Additional Functions; Belt Failure Detection Without Sensor - Siemens SED2 Commissioning Manual

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

7.8.1 Parameter changes

Start with quick commissioning according to application 1
Par. no.
Value Parameter function
P0501(0) 4
Type of sensor
P0701(0) 16
Function of digital input 1 in "Auto" mode Set DIN 1 for fixed freq SP + ON
P0756(0) 0
Analog input
P1080
5
Motor minimum frequency
P1210
3
Restart after fault / mains break
P2200
1
Enable PID controller
P2201
60
Fixed PID setpoint
P2253
2224
PID setpoint
P2264
755.0
PID feedback
P2274
0
PID derivative action time
P2280
1.5
PID proportional band
P2285
20
PID integral action time
P2306
0
PID acting direction
P2390
20
Hibernation frequency
P2391
60
Hibernation timer
P2392
-5
Restart PID controller deviation
r2262
Filtered PID setpoint
r2272
PID scaled feedback
r2273
PID error
r2294
PID output
8

Additional functions

8.1 Belt failure detection without sensor

Carry out quick commissioning and modify the parameters for normal operation, then proceed as follows:
Frequency /
torque curve
Siemens
Building Technologies
Torque [Nm]
P2189
Upper torque threshold 3
P2190 unterer
Lower torque threshold 3
P2187
Upper torque threshold 2
P2188
Lower torque threshold 2
P2185
Upper torque threshold 1
P2186
Lower torque threshold 1
P2182
Threshold frequency 1
Commissioning Guide
8 Additional functions
Function selection
Set input scale to range of QBE620 – P25
Unipolar voltage input (DC 0...10 V)
Minimum frequency
Auto restart after mains fail
Enable PID loop
Fixed setpoint as a percentage of sensor range
PID setpoint source
Sets PID feedback source to AIN-1
Derivative action time
Proportional band
Integral action time
Direct acting loop
Hibernation setpoint [%]
Hibernation timer in seconds
Restart – PID error in %
Display actual setpoint in C
Display actual condenser pressure
Display actual PID error in %
Display actual VSD output in %
Frequency [Hz]
P2183
P2184
Threshold frequency 2
Threshold frequency 3