Siemens SED2 Commissioning Manual page 82

Variable speed drives
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

P1213
Restart time increment
Selects the amount the restart time is incremented for each restart of the VSD if P1210 is set
to 3, 4 or 6.
Unit: s
Min: 0
P1230[2]
BI: Enable DC braking
Enables DC braking via a signal applied from an external source. Function remains active
while external input signal is active.
DC braking causes the motor to stop rapidly by applying a DC braking current (current
applied also holds shaft stationary).
When the DC braking signal is applied, the VSD output pulses are blocked and the DC
current is not applied until the motor has been sufficiently demagnetized.
Unit: -
Min: 0:0
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P1230[0]: VSD in "Auto" mode
Caution:
Frequent use of long periods of DC braking can cause the motor to overheat.
Note:
This delay time is set in P0347 (demagnetization time). If this delay is too short, overcurrent trips can occur.
P1232
DC braking current
Defines the level of DC current in [%] relative to the rated motor current (P0305).
Unit: % Min: 0
P1233
Duration of DC braking
Defines duration for which DC injection braking is to be active following an OFF1 command.
Unit: s
Min: 0
Value:
P1233=0: Not active following OFF1
Caution
Frequent use of long periods of DC braking can cause the motor to overheat.
Note:
The DC braking function causes the motor to stop rapidly by applying a DC braking current (the current applied also
holds the shaft stationary). When the DC braking signal is applied, the VSD output pulses are blocked and the DC
current not applied until the motor has been sufficiently demagnetized (demagnetization time is calculated automatically
from motor data).
P1236
Compound braking current
Defines DC level superimposed on AC waveform. The value is entered in [%] relative to rated
motor current (P0305).
Unit: % Min: 0
Value:
P1236=0: Compound braking disabled
P1236=1 - 250: Level of DC braking current defined as a [%] of rated motor current (P0305)
Dependency:
Active after OFF1 / OFF3 command
Note:
Increasing the value will generally improve braking performance; however, if you set the value too high, an overcurrent
trip may result.
P1240
Configuration of Vdc controller
Enables / disables Vdc controller.
Unit: -
Min: 0
Details:
The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia systems.
Settings:
0=Vdc controller disabled
1=Vdc-max controller enabled
Note:
Vdc max automatically increases ramp-down times to keep the DC link voltage (r0026) within limits (P2172).
P1260
Source of changeover control
Selects the possible sources for contactor changeover control.
Unit: -
Min: 0
Settings:
0
Bypass disabled
1
Controlled by VSD trip
2
Controlled by DIN – see P1266
3
Controlled by DIN and VSD trip
4
5
See note below
6
7
Note:
When using setting 4...7, the setpoint is to be preset via the USS protocol (BOP or COM link) or the motor
potentiometer. Analog presettings of setpoints are not possible.
r1261
BO: Contactor control word
Output word from the bypass feature that allows external connections to be made.
Unit: -
Min: -
Bit fields:
Bit00
Bit01
P1262
Bypass dead time
Time delay between switching contactors to allow motor to demagnetize.
Unit: s
Min: 0
82 / 100
Siemens
Building Technologies
Def: 30
Def: 0:0
Def: 100
Def: 0
Def: 0
Def: 1
Def: 0
Def: -
Motor supplied by VSD
Motor supplied by mains
Def: 1.000
Commissioning Guide
10 Parameterization
Max: 1000
Max: 4000:0
P1230[1]: VSD in "Hand" mode
Max: 250
Max: 250
P1233=1 - 250: Active for the specified duration
Max: 250
Max: 3
2=reserved
3=reserved
Max: 7
Max: -
0
YES,
1
NO
0
YES,
1
NO
Max: 20.000
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 2
Level 2
Level 2
CM1G5192en
29.07.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents