Technical Manuals Online! - http://www.tech-man.com
AH1OADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 43, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1OADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 44, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1RADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 45, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1RADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 46, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1EADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 47, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1EADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 48, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1Rfan.OVR.On = SwitchState
If mid(InBuffer, SWS + 49, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH1Rfan.OVR.Off = SwitchState
If mid(InBuffer, SWS + 50, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
Zone1.PRS = SwitchState
If mid(InBuffer, SWS + 51, 1) = "A" and Main.Key then ~
SwitchState = On Else SwitchState = Off
Zone1.EXH = SwitchState
If mid(InBuffer, SWS + 52, 1) = "A" then SwitchState = On Else ~
SwitchState = Off
Zone1.CON = SwitchState
If mid(InBuffer, SWS + 53, 1) = "A" then SwitchState = On Else ~
SwitchState = Off
Zone2.CON = SwitchState
5-16
Smoke Control Programs
Infinity Smoke Control Guide
TOC