Controller Status Indicators

Each of the Infinity controllers in the smoke control system has a
number of status indicators. The following is a brief summary of some
of the more commonly used indicators. For more information, refer to
the controller's installation guide.

On the Door of the CX9200

SCAN - Flashes once for every scan of the controller.
ERROR - Turns on when a system error occurs.
Energynet - Turns on when Energynet is receiving data.
Programmable Status LEDs - There are eight programmable status
LEDs on the front door of the CX9200. These LEDs are controlled
through Plain-English programs by turning the system variables Status1
through Status8 OFF and ON. In our example system, the following
Status LEDs were programmed:
• Status1 - Programmed to turn on when the FSCS audible
annunciator is on. This occurs when there is an equipment fault, an
Infinet controller is off-line, or an Infinet controller has an output
overriden.
• Status2 - Programmed to turn on when there is a communications
fault with the FSCS.
• Status4 - Programmed to turn on when there has been a self-test
failure.

Inside the CX9200

SCAN - Flashes once for every scan of the controller.
ERROR - Turns on when a system error occurs.
CPU - Flashes every 0.2 seconds to show that the CPU is operating
properly.
Energynet LEDs- There are five LEDs inside the CX9200 that indicate
the status of Energynet: RD, POL, TD, COL, TP.
6-10
System Operation
Infinity Smoke Control Guide