File Explanation:
This data file contains the CX9200 numerics that are used to set the state
of all of the LEDs on the FSCS. If the numeric is turned ON, the
corresponding LED on the FSCS will turn ON.
The position of the numeric in the file must correspond to the LED
Addresses for that LED. The LED Adrress is determined by the internal
FSCS wiring from the LED to the I/O card. The FSCS manufacturer will
supply you with the LED Addresses. Since the I/O cards have 80 points
each, there should be 80 entries in LampPointMap for each I/O card.
For example, the LED Addresses for this example are as follows:
LED 0 --> SpareLamp (not used)
LED 1 --> AH3Sfan.ON (AHU3 Supply Fan STATUS LED)
LED 2 --> AH3Sfan.Fail (AHU3 Supply Fan FAIL LED)
LED 3 --> AH2Sfan.ON (AHU2 Supply Fan STATUS LED)
.
.
LED 80 --> Horn (Audible Annunciator)
The last output, called "Horn", controls the state of the audible
annunciator on the FSCS.