Other Features
The FSCS will also have the following features:
• Master Key – This key will silence the audible alarm and enable all
of the controls on the FSCS. This key must be made available to
authorized personnel only.
• Clear Faults Button -- This momentary push-button will clear all of
the fault indicators on the FSCS. This push-button is not enabled
unless the Master key is ON. If the fault corrects itself, the fault
indicator will automatically turn off. If the fault returns, the fault
indicator will turn on again. If there is a fault detected during the
weekly self-test of a dedicated controller, the fault indicator for that
piece of equipment will stay on until it is cleared. The Clear Faults
push-button is wired to an input on the FSCS, just like any other
switch.
• Lamp Test Button - This momentary push-button turns on all of the
status indicators on the FSCS, thus allowing the operator to
determine if there is a bad indicator.
• Audible Alarm – The alarm sounds when there is a smoke emergency
or when there is an equipment fault. Turning the Master key ON is
the only way to silence the alarm.
Ordering Information
Andover Controls' UL listing includes a custom FSCS panel that is
manufactured by Automation Displays Incorporated. For ordering
information, contact:
Automation Displays Inc.
3533 North White Avenue
Eau Claire, Wisconsin 54703
(715) 834-9595
2-14
Infinity Smoke Control System Components
Infinity Smoke Control Guide