TOC
System Operation
R> Print Zone1.ALM,Zone2.ALM,Zone3.ALM
Zone1.ALM = Off
Zone2.ALM = Off
Zone3.ALM = Off
Modifying Point Values
You can also modify the value of a point from the Command window by
typing name = value <cr>.
For example:
R> MaxCtlrTime = 8
R> MaxFanTime = 40
If a program or function is setting the value of the point, the value will
get changed back by the program or function. See Disabling and
Enabling Points or Files for information on how to override the program
control.
Enabling and Disabling Points and Files
If you want to halt the execution of a program for debugging purposes,
you can type Disable filename <cr> in the Command window. In
order to re-start the program, type Enable filename <cr>.
For example:
R> Disable HornControl
R> Enable HornControl
If you want to prevent a program from updating a point value so you can
modify the point, or you want to modify the value of an input or output
point, you can type Disable name <cr> in the Command window.
Type Enable name <cr> if you want the points to back under system
control. This is very useful if you are debugging or testing a program
and want to see how the program reacts to the points that are used in it.
For example:
R> Disable Zone4.PRS
R> Enable Zone4.PRS
6-14
Infinity Smoke Control Guide
Technical Manuals Online! - http://www.tech-man.com