Andover Controls Infinity Manual page 182

Smoke control
Table of Contents

Advertisement

Table B-4. TCX840
NAME
VAVDmp.Opn
VAVDmp.Cls
VAVDmp
DefaultDmprPosn
Table B-5. TCX861
NAME
Damper
Damper.Opn
Damper.Cls
DamperPosition
DefaultDmprPosn
PowerFail
Table B-6. TCX853
NAME
SfanSt
Sfan
DefaultFanPosn
B-10
Technical Manuals Online! - http://www.tech-man.com
FLR2TCX
or TCX851
TYPE
DESCRIPTION
Input 1
VAV Damper OPEN Proof Sensor
Digital
Input 2
VAV Damper CLOSED Proof Sensor
Digital
Output 4
VAV Damper Control
TriState
Numeric
VAV Damper Position when NOT Performing
Smoke Control
FLR4TCX
Points
TYPE
DESCRIPTION
Output 6
Motorized VAV Damper Control
Voltage
Numeric
VAV Damper OPEN Indicator based on Hall-
Effect Sensor Feedback
Numeric
VAV Damper CLOSED Indicator based on Hall-
Effect Sensor Feedback
Numeric
VAV Damper Position that is Equal to Damper
Overridevalue
Numeric
VAV Damper Position when NOT Performing
Smoke Control
System
Power Indicator Flag used to Trigger the
Variable
AutoLearn Program
AHU3
Points
TYPE
DESCRIPTION
Input 1
Supply Fan Differential Pressure Proof Sensor
Digital
Output 1
Supply Fan Control
Digital
Numeric
Supply Fan State when NOT Performing Smoke
Control
Example System Points
FLR3TCX
Points
Infinity Smoke Control Guide