' Plant 8
If not (((AHU1 RADmp = On) and (AHU1 RADmp.Opn <> On))
or ((AHU1 RADmp = -On) and (AHU1 RADmp.Cls <> On))) then
PlantTimer[8] = Time
AH1RADmp.Fail = (Time - PlantTimer[8]) > MaxDamperTime
' Plant 9
If not (((AHU2 OADmp = On) and (AHU2 OADmp.Opn <> On))
or ((AHU2 OADmp = -On) and (AHU2 OADmp.Cls <> On))) then
PlantTimer[9] = Time
AH2OADmp.Fail = (Time - PlantTimer[9]) > MaxDamperTime
' Plant 10
If not (((AHU2 EADmp = On) and (AHU2 EADmp.Opn <> On)) or
((AHU2 EADmp = -On) and (AHU2 EADmp.Cls <> On))) then
PlantTimer[10] = ~
Time
AH2EADmp.Fail = (Time - PlantTimer[10]) > MaxDamperTime
' Plant 11
If not (((AHU2 RADmp = On) and (AHU2 RADmp.Opn <> On))
or ((AHU2 RADmp = -On) and (AHU2 RADmp.Cls <> On))) then
PlantTimer[11] = ~
Time
AH2RADmp.Fail = (Time - PlantTimer[11]) > MaxDamperTime
' Plant 12
If not (((SMKDMPRS Fl2.SASDmp = On) & (SMKDMPRS
Fl2.SASDmp.Cls <> On)) or ((SMKDMPRS Fl2.SASDmp = Off) &
(SMKDMPRS Fl2.SASDmp.Opn ~
<> On))) then PlantTimer[12] = Time
FL2SADmp.Fail = (Time - PlantTimer[12]) > MaxDamperTime
' Plant 13
If not (((SMKDMPRS Fl2.RASDmp = On) & (SMKDMPRS
Fl2.RASDmp.Cls <> On)) or ((SMKDMPRS Fl2.RASDmp = Off)
& (SMKDMPRS Fl2.RASDmp.Opn ~
<> On))) then PlantTimer[13] = Time
FL2RADmp.Fail = (Time - PlantTimer[13]) > MaxDamperTime
' Plant 14
If not (((SMKDMPRS Fl3.SASDmp = On) & (SMKDMPRS
Fl3.SASDmp.Cls <> On)) or ((SMKDMPRS Fl3.SASDmp = Off) &
(SMKDMPRS Fl3.SASDmp.Opn ~
<> On))) then PlantTimer[14] = Time
5-24
Smoke Control Programs
Infinity Smoke Control Guide