Protective Extra-Low Voltage As Protection Against Electric Shock - Bosch Rexroth IndraMotion MTX micro Easy Setup Manual

For standard turning and milling machines
Hide thumbs Also See for Rexroth IndraMotion MTX micro:
Table of Contents

Advertisement

DOK-MTXMIC-EASY*******-CO06-EN-P
IndraMotion MTX micro Easy Setup for Standard Turning and Milling Machines
4.3.2

Protective extra-low voltage as protection against electric shock

Secure built-in devices from penetrating foreign objects and water, as
well as from direct contact, by providing an external housing, for exam‐
ple a control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injury
by electric shock!
Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipment
grounding conductor at the grounding points.
Connect the equipment grounding conductor of the components of the
electric drive and control system permanently to the main power supply
at all times. The leakage current is greater than 3.5 mA.
Establish an equipment grounding connection with a minimum cross
section according to the table below. With an outer conductor cross sec‐
tion smaller than 10 mm
equipment grounding conductors is allowed, each having the same
cross section as the outer conductors.
Cross section outer con‐
ductor
1.5 mm
(16 AWG)
2
2.5 mm
2
(14 AWG)
4 mm
2
(12 AWG)
6 mm
2
(10 AWG)
10 mm
2
(8 AWG)
16 mm
(6 AWG)
2
25 mm
2
(4 AWG)
35 mm
2
(2 AWG)
50 mm
2
(1/0 AWG)
70 mm
2
(2/0 AWG)
...
Tab. 4-1:
Minimum cross section of the equipment grounding connection
Protective extra-low voltage is used to allow connecting devices with basic in‐
sulation to extra-low voltage circuits.
On components of an electric drive and control system provided by Bosch
Rexroth, all connections and terminals with voltages up to 50 volts are PELV
("Protective Extra-Low Voltage") systems. It is allowed to connect devices
equipped with basic insulation (such as programming devices, PCs, note‐
books, display units) to these connections.
Bosch Rexroth AG
Safety instructions for electric drives and controls
2
(8 AWG), the alternative connection of two
Minimum cross section equipment grounding conductor
Leakage current ≥ 3.5 mA
1 equipment grounding
conductor
10 mm
2
(8 AWG)
16 mm
2
(6 AWG)
25 mm
2
(4 AWG)
35 mm
2
(2 AWG)
...
25/177
2 equipment grounding
conductors
2 × 1.5 mm
(16 AWG)
2
2 × 2.5 mm
2
(14 AWG)
2 × 4 mm
2
(12 AWG)
2 × 6 mm
2
(10 AWG)
-
-
-
-
-
-
...