Kl2532 - Led Displays; Fig. 4 Kl2532 - Leds - Beckhoff KL2532 Documentation

Two channel power stage terminals for dc motors
Table of Contents

Advertisement

Product overview
2.4

KL2532 - LED displays

Fig. 4: KL2532 - LEDs
LED
Display
Run (green)
reserved
Enable A (green) off
on
Warning A
on
(yellow)
Error A (red)
on
Power (green)
off
on
Enable B (green) off
on
Warning B
on
(yellow)
Error B (red)
on
14
Data transmission on the K-bus is active
Channel 1 is either not enabled or not ready to operate.
Channel 1 is enabled and is ready to operate.
The internal temperature has risen to more than 80 °C, or the power supply
voltage has dropped.
There is an error at channel 1
The power supply voltage is absent (less than 7 V).
The power supply voltage is present (more than 8 V).
Channel 2 is either not enabled or not ready to operate.
Channel 2 is enabled and is ready to operate.
The internal temperature has risen to more than 80 °C, or the power supply
voltage has dropped.
There is an error at channel 2
Version: 3.2.0