Kl2535 - Led Displays; Fig. 2 Kl2535 - Led Displays - Beckhoff KS2535, KL2545 Manual

Pulse width current terminals
Table of Contents

Advertisement

Product overview
2.3

KL2535 - LED displays

Fig. 2: KL2535 - LED displays
LED
Display
Run (green)
reserved
Enable A (green) off
on
-
reserved
Error A (red)
on
Power (green)
off
on
Enable B (green) off
on
Warning (yellow) on
Error B (red)
on
10
Data transmission on the K-bus is active
Channel 1 is either not enabled or not ready to operate.
Channel 1 is enabled and is ready to operate.
There is an error at channel 1
The power supply voltage is absent (less than 7 V).
The power supply voltage is present (more than 8 V).
Channel 2 is either not enabled or not ready to operate.
Channel 2 is enabled and is ready to operate.
The internal temperature has risen to more than 80°C, or the power supply
voltage has dropped.
There is an error at channel 2