Kl4132 - Connection And Led Description; Fig. 10 Kl4132 - Connection And Leds - Beckhoff KL4132 Documentation

Dual-channel analog output terminal, -10 v to +10 v, 16 bit
Table of Contents

Advertisement

3.5

KL4132 - connection and LED description

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting,
disassembly or wiring of the Bus Terminals!
WARNING
Fig. 10: KL4132 - connection and LEDs
Connection KL4132
Terminal point
No.
Output1
1
n.c.
2
GND
3
Shield
4
Output2
5
n.c.
6
GND
7
Shield
8
LED description KL4132
LED
Color
Run1 LED
green
Run2 LED
KL4132
Comment
+ Output 1
Not used
Internal ground (internally connected to terminal point 7)
PE contact (internally connected to terminal point 8)
+ Output 2
Not used
Internal ground (internally connected to terminal point 3)
PE contact (internally connected to terminal point 4)
Description
On:
Normal operation
Off:
Watchdog timer overflow has occurred. If no process data is transmitted to the bus cou-
pler for 100 ms, the green LEDs go out. The output assumes a user-specified voltage
(see Feature register [} 30]).
Version: 3.0
Mounting and wiring
19

Advertisement

Table of Contents
loading