Emergencies
Regular generator inspections
➤ Adhere to the given inspection intervals for safe generator operation:
■
Daily check by authorised personnel:
─
Insulation monitor function check.
■
Annual inspection by trained and authorised electrician:
─
Visual check for mechanical damage to the generator and control box.
─
Visual check for damage to the insulation of connecting cables.
─
Earth conductor check.
─
Insulation resistance measurement.
─
Earth conductor current measurement.
─
Leakage current measurement.
─
Generator function check.
─
Check the generator fan and clean if necessary.
─
Check all screwed connections on the generator and control box and tighten if necessary.
─
Check that all warning and other labels are complete ands undamaged.
Emergencies
Correct fire fighting
Suitable extinguishing agents:
■
Foam
■
Carbon dioxide
■
Sand or earth
Unsuitable extinguishing agents:
■
Strong jet of water
1. Keep calm.
2. Give the alarm.
3. Shut down the machine from the instrument panel if possible.
4. To ensure safety:
■
warn persons in danger
■
help incapacitated persons
■
close the doors
5. Try to extinguish the fire if you have the skill to do so.
Contact with operating fluids/materials
The following operating fluids/materials are in the machine:
■
Fuel
■
Engine coolant
■
Battery electrolyte
■
Lubricating oil
■
Compressor cooling oil