Safety and Responsibility
3.8

Generator operation

Generator operation

Protection against dangerous electric current

Protection against dangerous electric current is regulated by
IEC 60364–5–551 (DIN VDE 0100–551).
The measures concerning isolation, insulation monitoring and shut-down are applied. The generator
is equipped with an automatic mains cut-out with overcurrent release and insulation monitoring in
accordance with this protective measure.
➤ Observe and follow the regulations concerning protection against dangerous electric current
when using the generator.

Instructions for safe generator operation

➤ Take note of the following for safe generator operation:
Check correct function of the insulation monitoring device daily.
Do not earth the neutral line (N) or connect it to the common protective earth/equipotential
bonding (PE).
Make sure the equipotential bonding to earth is properly carried through (mains and machine
through cable to consumer).
If the generator feeds a network (TN network), let the network's protective measures remain
effective or create another protective measure that is effective.
Adjust the protective measures accordingly if the generator feeds a different network.
Only a qualified electrician is allowed to carry out work on the generator or generator control
box. The electrician is responsible for the effectiveness of the protective measures provided.
Follow the regulations of the local electricity supply utility and obtain any necessary permits.
When cleaning the inside of the machine do not direct water or steam jets directly at the
generator or terminal box.
Check regularly that all electrical connections are tight and in order.

Connection of extension cables

➤ Observe and adhere to the regulations regarding extension cables before operating the gener‐
ator.
In IT networks, the total length of power cables may not exceed 250 m ((DIN VDE 0100, Part
728 / IEC 60364-5-551).
Use at least H07RN-F cables to DIN VDE 0282 Part 4 (IEC 60245-4 / HD 22.4) as non-fixed
extension cables.

Maximum power supply loading

➤ Observe the following for maximum power supply loading of connected consumers:
The power consumption values of simultaneous consumers are added.
The maximum continuous power loading on the generator by the connected consumers is
limited by the safety cut-out.