Dimensions And Weights - Eaton Magnefix MD4 User Manual

Medium-voltage switchgear
Table of Contents

Advertisement

Magnefix MD4
2.3.2

Dimensions and weights

Dimensions – upright version
Panel name
Cable panel (including switch caps)
Busbar connection
Connecting panel
Busbar connecting panel (sectional panel including switch caps)
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
Busbar connecting panel with SVS or HC switchgear
Height
Depth with fuse panel
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator)
Depth with protected panel (including earthing interlock)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where:
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
16
991.184 G01 03
K: number of cable panels
T: number of protected branches
rd
support point) or maximum weight: 240 kg.
width
91 mm
91 mm
91 mm
182 mm
19.5 kg
61.5 kg
230 mm
37.5 kg
91 mm
1517 mm
517 mm
423 mm
570 mm (+ 27)
weight
15 kg
7.5 kg
4.5 kg
9 kg

Hide quick links: