Page 10
24. Battery Charger
Provides an automatic battery charger for engine crank-
ing batteries. Requires a separate 100-135Vac, 60Hz
customer supplied power source.
C. Battery Charger with 12Vdc Output: Provides an
automatic battery charger with 12Vdc, 5 amp out-
put.
D. Battery Charger with 24Vdc Output: Provides an
automatic battery charger with 12Vdc, 5 amp out-
put.
When supplied, the battery charger is provided in a sep-
arate wall mounted enclosure (Figure 3-9). Separate
instructions and wiring information are provided with the
charger for installation purposes.
NOTICE
A separate 120 VAC control power supply is
required for the battery charger input. No connec-
tions between the transfer switch and battery charg-
er should be made.
34. Logic Extender Cable
Provides logic extender cables with connectors which
permit remote mounting of the Automatic Transfer
Controller in non-standard applications.
6.13 (156)
8.25 (208)
9.50 (241)
7.25 (182)
8.88 (223)
7.50 (191)
Figure 3-9 Charger Mounting Dimensions in Inches
(mm)
A. 48 inch (1219 mm): Provides logic extension cable
with connectors.
B. 72 inch (1829 mm): Provides logic extension cable
with connectors.
C. 96 inch (2438 mm): Provides logic extension cable
with connectors.
D. 120 inch (3048 mm): Provides logic extension cable
with connectors.
E. 144 inch (3658 mm): Provides logic extension cable
with connectors.
Special lengths are available. Contact Cutler-Hammer.
37. Service Entrance Rated Transfer Switch
Provides the label "Suitable for use as Service
Equipment" and the features necessary to meet the
requirements for the label. Includes service disconnect
with visible indication and neutral assembly with remov-
able link. Feature 16B or 16N must be selected sepa-
rately.
A. Service Equipment Rated Transfer Switch without
Ground Fault Protection: Provides Service
Equipment rating for an application that does not
require ground fault protection.
B. Service Equipment Rated Transfer Switch with
Ground Fault Protection: Provides Service
Equipment rating for an application that requires
ground fault protection.
41. Space Heater with Thermostat
Provides a space heater and adjustable thermostat.
External control power is not required.
A. Space Heater with Thermostat - 100 Watts:
Provides 100 watt space heater with an adjustable
thermostat.
B. Space Heater with Thermostat - 200 Watts:
5.25 (132)
7.38 (187)
Provides 200 watt space heater with an adjustable
thermostat.
C. Space Heater with Thermostat - 400 Watts:
Provides 400 watt space heater with an adjustable
thermostat.
42. Seismic Certification
Provides a Seismic certified Transfer Switch with certifi-
cate for application is Seismic Zone 4 under the California
Building Code, the Uniform Building Code and BOCA.
IB01602002E
Effective 10/02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Atvispa32000xsu

Table of Contents