Technical Data Cutler-Hammer Effective: May 1998 Page 1 Magnum DS New Information Mailed to: E, C/32-000B Metal-Enclosed Low-Voltage Switchgear TD.44A.01.T.E...
4000 ond each, with a 15-second interval of MDS-850 4000 zero current between the two periods. MDS-C50 5000 Table R5 – Magnum DS Breaker Control Voltages and Currents Control Voltage 24 DC 48 DC 125 DC 120 AC 240 AC Close current (SR), ampere 2.70...
Instantaneous (I) Short delay (S) Ground (G) Ground Alarm only (GA) Every Magnum DS trip unit comes standard with LSI characteristics. Optional ground (G) or ground alarm (GA) may also be provided. These trip units also provide the ability to defeat instantaneous protection.
Low-Voltage Switchgear Ratings Table R10 – Magnum DS Circuit Breakers with Digitrip RMS 520 Trip Unit Typical Long Delay and Short Delay Time/Phase Current Characteristic Curve (LS) 1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself.
Page 7
Low-Voltage Switchgear Ratings Table R11 – Magnum DS Circuit Breakers with Digitrip RMS 520 Trip Unit Typical Instantaneous Time/Phase Current Characteristic Curve (I) 1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself.
Page 8
Effective: May 1998 Low-Voltage Switchgear Ratings Table R12 – Magnum DS Circuit Breakers with Digitrip RMS 520 Trip Unit Typical Ground Fault Time/Phase Current Characteristic Curve (G) 1. The end of the curve is determined by the interrupting rating of the circuit breaker.
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 9 Low-Voltage Switchgear Ratings Table R13 – Metering Type Current Transformers for Mounting in Circuit Breaker Compartments ANSI Meter Accuracy Classification Breaker Frame Rating Ratio Ratio B-0.1 B-0.2 B-0.5 B-0.9 B-1.8...
Current Standards 4. Excessively high or low ambient Correction Correction Feet Meters temperatures. Magnum DS circuit breakers meet or exceed all applicable requirements of 6,600 2,000 1.000 1.000 For ambient temperatures exceed- ANSI Standards C37.13, C37.17, C37.50 ing 40°C, and based on a standard...
Transformer kVA – 112.5 through 3750 transition section. For these situations, of transformers eliminates necessity Low-Voltage – 208, 240, 480 or 600 V Magnum DS switchgear is designed to of vaults accommodate close coupling to dry Unit Substations may be indoor or out-...
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Page 12 Effective: May 1998 Low-Voltage Switchgear Application Types of Systems A. Simple Radial Simplest and least costly Easy to coordinate B. Primary Selective Radial Similar to simple radial, with added advantage of spare primary incoming cable circuit.
Most Magnum DS Switchgear is fed mary switch or breaker, for mainte- of the associated main breakers. The from power transformers. To facilitate interrupting rating should be at least nance purposes.
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Page 14 Effective: May 1998 Low-Voltage Switchgear Application Feeder Breakers – General Motor Starting Feeder Breakers Group Motor Feeder Breakers Circuit breakers for feeder circuit pro- These breakers are usually electrically Typical loads for such circuits are...
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 15 Low-Voltage Switchgear Application Figure A1. Three-Wire Distribution, Delta Source (Ungrounded) Figure A4. Three-Wire Distribution, Solidly Grounded System Blown Fuse Ground Current Still Flows Through Load Figure A5. From Other Fuses Figure A2.
Page 16
If a second ground occurs on able. If the Magnum DS breaker solid- to main breakers may assure good another phase, and exceeds the state tripping system including an ground protection.
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 17 Low-Voltage Switchgear Application been cleared, the timer will run. It has a High-Resistance Grounding When one phase becomes grounded, range of 2–48 hours. When the timer additional current above the charging...
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Page 18 Effective: May 1998 Low-Voltage Switchgear Application Application note: It may not be possi- Ground Fault During fault conditions, each trip unit ble to precisely locate faults within a that senses the fault sends a restrain- When the sensing circuit detects a conduit.
Page 19
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 19 Low-Voltage Switchgear Application 600/347 (Max.) Wye 600/347V (Max.) Wye To Distribution Equipment To Distribution Equipment Control Control Circuit Circuit Pulser Grounding Test Pulser Grounding Test Resistor Resistor Resistor Resistor...
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Page 20 Effective: May 1998 Low-Voltage Switchgear Application The Following Provides Guidelines for Ground Fault Protection. System Advantages Disadvantages Equipment Available for Protection Main Breaker Tie Breaker Fdr. Breaker Notes Ungrounded Minimum distur- When ground detector...
Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 23 Low-Voltage Switchgear Application Application of Magnum DS Power Circuit Breakers With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types Transformer Base Secondary Short-Circuit Currents Minimum Size Breakers for Selective (100%) Rating...
Page 24
Metal-Enclosed Page 24 Effective: May 1998 Low-Voltage Switchgear Application Application of Magnum DS Power Circuit Breakers With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types, Continued Transformer Base Secondary Short-Circuit Currents Minimum Size Breakers for Selective (100%) Rating...
Page 25
Metal-Enclosed Effective: May 1998 Page 25 Low-Voltage Switchgear Application Application of Magnum DS Power Circuit Breakers With Standard Three-Phase Transformers – Fluid Filled and Ventilated Dry Types, Continued Transformer Base Secondary Short-Circuit Currents Minimum Size Breakers for Selective (100%) Rating...
Heavy Duty Hinge Pins Optional Mechanical Interlock — Available between adjacent breakers. Rear Cover/Doors — In Magnum DS Switchgear standard rear covers with captive hardware are the bolt-on type. They are split into two sections to facil- itate handling during removal and installation.
Stand-Off Insulation System — Bus Ampacities — Vertical and cross Glass reinforced polyester has been bus ratings in Magnum DS are 2000, used on both low- and medium-volt- 3200, 4000, and 5000 amperes. In addi- age switchgear for decades. By com-...
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 35 Low-Voltage Switchgear Features – Wiring Cable Compartment — The cable com- For applications involving excessive Control Wire — Standard wire is Type partment gives ample room for termi- wiring, or nonstandard terminal SIS insulated stranded copper, extra nating the power cables.
Features – Accessories Features – Instrumentation/ Metering and Options mounted on the Instrument compart- Flexibility — Magnum DS Switchgear ment door or on a the panel of a blank Switchgear Accessories — Standard allows for a variety of metering cell.
The De-ion principle is incorporated This means that the energy required to in all Magnum DS circuit breakers. This open the breaker is always prestored makes possible faster arc extinction for following a closing operation.
Page 38
Metal-Enclosed Page 38 Effective: May 1998 Low-Voltage Switchgear Features – Breaker Magnum DS Switchgear – Trip Units Trip Functions — Magnum DS trip c. Compartment position switch, 6 or units provide the maximum in flexibil- 12 contact, actuated by movement Digitrip RMS Trip Unit —...
Page 39
Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 39 Low-Voltage Switchgear Features Trip Close Control Power Figure F1: Typical Control Diagram for Magnum DS Electrically Operated Breaker INCOM INCOM Neg. Neutral Source Zone Shunt Spring Motor Cell Switch Contacts Power...
(silver-plated) (tin- Removable Element — The removable having one or more individual breaker plated) copper bar mounted on heavy- element shall consist of a Magnum DS or instrument compartments, and a duty supports, and having bolted power circuit breaker equipped with rear compartment for the buses and joints.
Page 41
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Effective: May 1998 Page 41 Low-Voltage Switchgear Typical Specification Each breaker shall be equipped with a It shall be possible to test and verify Factory Assembly and Tests microprocessor-based, true RMS sens- the time and current characteristics The switchgear shall be completely ing trip device.
Page 42
Technical Data Cutler-Hammer Page 42 Effective: May 1998 TD.44A.01.T.E...
Page 43
Technical Data Cutler-Hammer Effective: May 1998 Page 43 TD.44A.01.T.E...
Page 44
Technical Data Magnum DS Cutler-Hammer Metal-Enclosed Page 44 Effective: May 1998 Low-Voltage Switchgear Cutler-Hammer TD.44A.01.T.E Printed in U.S.A.