Connect AC Power Cables Before Installing Tool-less Slide-
Rails in Sun Rack II 1042
Note -
X6-2 in the Sun Rack II 1042 (1000-mm) system rack. This procedure does not need to be
performed if you are installing the Oracle Server X6-2 in the Sun Rack II 1242 system rack.
Right-angle AC power cables must be installed before slide-rails when installing the Oracle
Server X6-2 into a Sun Rack II 1042 (1000-mm) system rack. The standard rail kit tool-less
slide-rails impede access to the 15kVA and 22kVA Power Distribution Unit (PDU) electrical
sockets in the 1000-mm rack. If you use the standard AC power cables and then install the
slide-rails into the rack, you will be unable to disconnect or remove the AC power cables.
You must use the following 2-meter right-angle AC power cable for this procedure:
7079727 - Pwrcord, Jmpr, Bulk, SR2, 2m, C14RA, 10A, C13

Connect AC Power Cables Before Installing Tool-less Slide-Rails in Sun Rack II 1042

You must perform the procedure in this section if you are installing the Oracle Server
Installing the Server Into a Rack
45