USER MAINTENANCE INSTRUCTIONS

OPERATING AND FAULT CODE DIAGNOSIS

There are 2 methods for confirming the cooler operation and
diagnosing faults on the cooler.
A. LED Display
There are two LED indicators on the main control board (located
in the control box) - refer below.
• Tri-Colour LED (upper LED) is used as an operational and
fault indicator. NOTE: Tri-colour LED double flashing Green
(every 2 seconds) = Normal Operation
• Red LED (lower LED) is used to indicate the condition of water
salinity and configuration of the water management system.
B. Wall Control Display
If controlled by a MagIQcool Wall Control, the wall control can
be used to enter the fault code history log, which details the last
four (4) faults in the system and the last four (4) types of faults
that have occurred.
The fault code history log may be entered at any time after the
cooler power has been turned ON. The fault code history log is
entered via the wall control using the following method:
1. Whilst the wall control is in "OFF" state, push and hold
"AUTO" and UP "▲" buttons simultaneously for at least one
(1) second.
2. After one (1) second "F1" and the word "Param" will be
displayed.
3. Pressing "AUTO" button will change "F1" to the current or
last fault code number e.g., "01" and the word "Param" will
change to the word "Value" this indicates the fault code
number that occurred.
4. Pressing "AUTO" button will return to the original "F1" and
"Param" display.
5. Pressing buttons marked UP "▲" or DOWN "▼" will scroll
through the fault log.
6. Fault indicators - "F1 to F4" - are the last four faults that were
recorded by the CPMD, and they might get repeated if the
fault has re-occurred. Fault indicators - "FA to Fd" - are the
last four types of faults that have occurred in this CPMD, and
they will only repeat if a different type of fault has occurred
since the last time this type of fault occurred.
7. If no buttons are pushed after sixty (60) seconds the wall
control will reset to the "OFF" state. The procedure to enter
the fault code history log must then be re-initiated.
8. Clear fault code once you have diagnosed the fault. Whilst
in fault code mode press and hold the "COOL" button for five
(5) seconds.

RED COLOURED LED

This LED indicates the status of the conductivity measurement
circuit and the status of the Salinity Control Method.
Salinity
LED
Control
Conductivity Circuit Status
Method
1 Flash then 2
Water Manager
Measured conductivity is below the conductivity
seconds OFF
set point
2 Flashes then
Water Manager
Measured conductivity is above the conductivity
2 seconds
set point
OFF
3 Flashes then
Fill count
Not measured
2 seconds
OFF
5 Flashes then
No water control function
2 seconds
OFF
Continuously
All
Lower probes are open circuit or conductivity is
ON
less than 9uS/cm
|
CW-P15 Indirect Evaporative Cooler 859740-G
31

TRI-COLOURED LED

This LED indicates the status of the cooler and indicates Fault
Codes (if applicable).
Cooler
Fault
LED
Status
Description
2 Green
Normal
The main program
flash
Operation
loop is running, no
then 2
Fault present.
seconds
OFF
1 Red
Communication
Wall Control: No
Flash
Failure
valid message for
then 2
10 seconds. System
seconds
shuts down.
OFF
2 Red
Failure to
Water has 20
Flashes
detect water at
minutes to reach the
then 2
low probe
LOW probe when
seconds
the solenoid valve
OFF
is on. If it fails to do
so the Fan motor
and pump shut down
and this Fault is
activated.
3 Red
Failure to
Once water has
Flashes
detect water at
reached the LOW
then 2
high probe
probe, water has
seconds
20 Minutes to reach
OFF
the HIGH probe. If
it fails to do so the
Fan motor and pump
shut down and this
Fault is activated.
4 Red
Failure to clear
When the drain has
Flashes
low probes
opened water has
then 2
during drain
20 minutes to clear
seconds
the LOW probe. If
OFF
it fails to do so the
Fan motor and pump
shut down and this
Fault is activated.
This will occur after
a timed Drain delay
when the Pump has
been switched off,
or during a Salinity
Drain.
5 Red
Water detected
Low probe is dirty
Flashes
at high probe
or faulty. If it fails
then 2
but not at low
to detect, the Fan
seconds
motor and pump
OFF
shut down and this
Fault is activated.
6 Red
Failure to clear
If after 4 hours of
Flashes
high probe
pump running water
then 2
has not cleared the
seconds
HIGH probe (i.e.
OFF
pumps not working),
If it fails to do so the
Fan motor and pump
shut down and this
Fault is activated.
7 Red
Motor Error
If an Error has
Flashes
Supply Fan
occurred in the
then 2
motor drive circuit.
seconds
OFF
MagIQcool
MagIQtouch
Fault Code
Fault Code
Fault Code #1
01
Fault Code #2
02
Fault Code #3
03
Fault Code #4
04
Fault Code #5
05
Fault Code #6
06
Fault Code #7
07