MAINTENANCE INSTRUCTIONS
• Back-off the cable gland through which the solenoid cable is
routed.
• Remove the metal electronics cover and the electronics
enclosure lid.
• Unplug all four cable terminations that are routed through the
left hand side conduit. This includes the chlorinator, water
management probe and solenoid valve cables.

CABLE REMOVAL

WARNING!
IT IS A SAFETY HAZARD to cut electrical cables to replace
electrical components, and will void warranty.
LOW VOLTAGE CABLE - (RHS port)
Chlorinator
Inlet
Solenoid
Core Block
Salinity
Probe
• Tape the ends of the cables together making sure the
connectors are staggered to form a tapered point.
|
CW-P15 Indirect Evaporative Cooler 859740-G
27
HIGH VOLTAGE CABLE - (LHS port)
ILL3565-A
ILL3565-A
Electronics
.
Control Box
• Pull the bundled cables through the conduit from the inlet side of
the cooler. Do not force the cable as damage to the connectors
may occur. If the cable becomes stuck, push it back through and
try re-taping the connectors.
ILL2276-A
ILL2276-A
• Reattach the connector to the bundle of cables and thread it back
up through the conduit and into the electronics enclosure area.
• Remove the faulty solenoid valve and cable from the bundle
and thread its connector through the cable gland.
• Replace the solenoid valve and thread the connector through the
cable gland. Tighten cable gland with minimal cable slack outside
tank.
• Unwind tape and plug the connectors back into the PCBA,
thread the cables into the slots in the electronics enclosure
and fasten the lid back into position.
ILL3566-A
• With the aid of a smear of lanolin, vaseline or silicon grease,
ILL3566-A
push the replacement solenoid valve into the rubber grommet
in the tank.
• Rotate the solenoid valve up and over the tab in the side wall.
• Put the electronics cover and solenoid cover back in position.
• Reconnect the water supply to the solenoid valve.
Cable Re-installation: Reverse of removal procedure.