USER MAINTENANCE INSTRUCTIONS
TRI-COLOURED LED - cont.
This LED indicates the status of the cooler and indicates Fault
Codes (if applicable).
Cooler
Fault
LED
Status
Description
8 Red
Warm Start
If the mains input
Flashes
voltage is under
then 2
90Vac but not low
seconds
enough to reset the
OFF
PCB, the system
switches off the
Fan and Pump
and indicates this
Fault. If the Voltage
returns to a usable
voltage level without
resetting the PCB
a Fault Code #8
is recorded in the
system log.
10 Red
Chlorinator
The Chlorinator is
Flashes
Fault
Short Circuit,
then 2
Open Circuit,
seconds
Degraded or has
OFF
Reached end of life.
This fault will
activate a 24 hour
clean tank drain
cycle until remedial
action is taken.
13 Red
Motor Error
If an Error has
Flashes
Exhaust Fan
occurred in the
then 2
motor drive circuit.
seconds
OFF
14 Red
Watering Cycle A watering cycle
Flashes
comprises the
then 2
circulation pump
seconds
time, core drain
OFF
time, tank fill time
and salinity check.
If the watering cycle
exceeds its preset
time, +1 is added
to a register. If the
next watering cycle
is completed on
time -1 is deducted
from register. If the
register >=3 then the
cooler will continue
to operate with a
warning symbol
displayed on the wall
control.
Check the water
supply to the cooler
is sufficient.
TRI-COLOURED LED - cont.
This LED indicates the status of the cooler and indicates Fault
Codes (if applicable).
MagIQcool
MagIQtouch
Fault Code
Fault Code
Fault Code #8
08
Fault Code
10
#'A'
Fault Code
13
#D
Fault Code
14
#'E'
Cooler
Fault
LED
Status
Description
15 Red
Pressure
If a Pressure sensor
Flashes
Sensor Fault
becomes blocked or
then 2
is partially blocked
seconds
the operation of
OFF
the CW could be
severally affected.
Fault Code #15 will
indicate that the
Pressure sensor
are not responding
within anticipated
boundaries for set
supply Fan speeds.
The 2 Pressure
sensors have
different failure
criteria.
SEELEY INTERNATIONAL - INSTALLATION MANUAL CW-P15 859740-G |
MagIQcool
MagIQtouch
Fault Code
Fault Code
Fault Code
15
#'F'