Seeley Climate Wizard CW-P15 Installation Operation & Maintenance page 27

Indirect evaporative cooler
Table of Contents

Advertisement

MAINTENANCE INSTRUCTIONS
• Reaching in through the top hatch opening, lift the front edge
of the spreader and remove from the core.
• Slide the middle core out through the opening at the front of
the cabinet.
• Slide the next core to the middle of the cabinet and remove
the spreader, the core can now be removed through the front
of the cabinet.
• Repeat with the remaining core.
Method - assembly
• Insert the new cores through the opening in the front of the
cabinet.
• Once each core has been installed into the centre position
assemble the spreader by hooking the rear flange into the
groove in the rear seal of the core.
ILL3542-A
ILL3542-A
ILL3543-A
ILL3543-A
ILL3544-A
ILL3544-A
ILL3545-A
• Move the outer cores as far as possible to the left and right to
leave the maximum gap possible for the third and final core.
• Insert the third and final core and spreader.
• Replace the cover utilities core inlet and screw into place. This
will keep the cores straight for the next step.
Note! For next steps, Core clamps MUST be engaged in the
correct order.
• Pull the front clamp lever towards you. This compresses the
cores. Lock the handle into the tab.
• Locate the rear core clamp handle extension and use it to swing
the rear clamp into position.
SEELEY INTERNATIONAL - INSTALLATION MANUAL CW-P15 859740-G |
ILL3546-A
ILL3546-A
ILL3547-A
ILL3547-A
ILL3548-A
ILL3549-A
ILL3548-A
ILL3549-A
ILL3550-A