Cleaning, Replacing And Checking The Water Management Probe; Clean Reservoir Interior; Clean Drain Pump - Seeley Climate Wizard CW-P15 Installation Operation & Maintenance

Indirect evaporative cooler
Table of Contents

Advertisement

MAINTENANCE INSTRUCTIONS
CLEAN CHLORINATOR cont
• Disengage earth tab on right-hand side of utilities cover,
remove utility cover screws, and remove cover.
• Unscrew the utilities mount and pull out bracket with
chlorinator attached.
• Unscrew the enclosure.
• Withdraw (and insert) the enclosure assembly on an angle as
shown above.
• Clean the chlorinator blades by gently wiping the contact
surfaces with a soft brush, cloth or non-abrasive wooden or
plastic implement. Be sure to clean the inner surfaces of the
chlorinator blades. Do not scratch or damage the metallic
surfaces of the chlorinator.
• Reverse above process to re-assemble.
ILL1963-A
CLEANING, REPLACING AND CHECKING THE
WATER MANAGEMENT PROBE
• Remove the small plastic shrouds from the first and third pins
• Clean the pins by wiping the contact surfaces with a soft cloth
• Check the probe pin resistances using a multi-meter (refer
• Resistance should be 0-0.5 ohms. A reading of 5 ohms or
• Check for shorts between pins: There should be an open
• Refit the shrouds over pins 1 & 3.
ILL3534-A
ILL3534-A

CLEAN RESERVOIR INTERIOR

ILL2928-A
Purpose:
To remove build-up of scale and deposits on the reservoir
(tank).
Method:
• Remove the middle core as per the procedure for core
• Additional cores may need to be removed to access all
• Remove the rubber bung in the bottom left hand corner of the
ILL2929-A
ILL2930-A
• Replace the rubber bung.
• Replace core(s) as per core replacement procedure.

CLEAN DRAIN PUMP

Purpose:
To clean the drain pump strainer after a period of time to
prevent restrictions to the water drain function.
Method:
Refer to replacing the drain pump section.
To expose the strainer for cleaning.
Note! There is no need to disconnect the pump electrical
ILL1963-A
cables.
- do NOT use abrasives
figure and wiring diagram - you'll need to unplug the probe
lead from the main PCB to do this)
greater indicates a faulty probe.
circuit
replacement
surfaces of the tank.
reservoir. Using a soft brush and hose, flush out the dirt and
deposits through the bung hole. Take care to prevent water
from entering the supply ducting.
SEELEY INTERNATIONAL - INSTALLATION MANUAL CW-P15 859740-G |
ILL1965-A
ILL1965-A
ILL3532-A
ILL3532-A
22