MAINTENANCE INSTRUCTIONS

INFREQUENT / PROGRAMMED MAINTENANCE

Replace cores

Purpose:
To remove and replace the cores that may have become
inefficient over time due to deposits and degradation of the
flocked surfaces.
Method - removal
• Turn off Power and water to the cooler.
• Remove filters as per filter replacement procedure.
• Remove "top seal filter frame".
• Remove "utilities cover"
• Remove "top hatch cover", the steel panel above the middle
core.
• Unplug hose snap fit connectors to each of the three
spreaders.
For the following steps there is an orange dot to demark
each of the clamp levers.
Note! It is important to disengage and re-engage core clamps in
the correct order. This will allow cores to release and compress
correctly to create an effective seal.
• Disengage core seal clamp on the outlet side of the cores by
lifting the mechanism handle upward.
|
CW-P15 Indirect Evaporative Cooler 859740-G
23
ILL3533-A
ILL3533-A
ILL3534-A
ILL3534-A
ILL3535-A
ILL3535-A
ILL3536-A
• Disengage the handle extension attached to the rear core clamp
from the front clamp lever.
• Using the handle extension, fold the rear clamp handle
towards the cooler outlet.
• Disengage the front clamp lever from its clip.
• Swing the front clamp lever towards the cooler outlet.
• Reach inside the top hatch cover and disengage the swinging
cam lock, see below. Pull the rails that seal against the top
seal of the cores up towards, away from the cores.
ILL3537-A
ILL3537-A
ILL3538-A
ILL3538-A
ILL3539-A
ILL3539-A
ILL3540-A
ILL3540-A
ILL3541-A