MAINTENANCE INSTRUCTIONS
REPLACE THE CHLORINATOR, PROBE AND
TORNADO PUMP
Purpose:
To replace faulty components
Method:
• Turn off Power to the cooler.
• Remove the utilities bracket as per the instructions for
cleaning the chlorinators.
• Remove the component that requires replacement.
• Replace the faulty component.
• Replace the cable as described in the solenoid valve
replacement procedure.

REPLACE THE DRAIN PUMP

Purpose:
To replace a faulty Tornado drain pump
(used to drain the reservoir)
Method:
• Turn off Power to cooler.
• Remove the Utilities Cover to gain access to the drain Pump.
• Slide off the plate that covers the pump by pushing down on
the plate to disengage it from a pair of tabs.
• Pull out the drain Pump.
• Remove the tube at the base of the pump.
• Remove the cover on the electronics enclosure to gain access to
the cable terminals.
ILL3570-A
• Unplug the drain pump terminals from the PCBA, noting the
ILL3570-A
position of the wires.
ILL3571-A
• Remove the cable gland on the side of the electronics
enclosure to allow the terminals to be threaded through the
gland.
ILL3571-A
ILL3572-A
• Tape the three terminals together in a staggered formation to
make it easier for the cable to be pulled through the conduit
without snagging.
ILL3572-A
SEELEY INTERNATIONAL - INSTALLATION MANUAL CW-P15 859740-G |
ILL3573-A
ILL3573-A
ILL3574-A
ILL3574-A
ILL3575-A
ILL3575-A
ILL3576-A
28