Siemens SINAMICS S150 NEMA Operating Instructions Manual page 74

Converter cabinet units 15hp-1250hp
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Electrical installation
4.6 Power connections
Figure 4-6
The line voltage assignments for making the appropriate setting on the fan transformer are
indicated in the following tables.
Note
Fan transformer for 660 to 690 V 3 AC
With the 500 V to 690 V 3 AC fan transformer, a jumper is inserted between the "600 V"
terminal and "CON" terminal. The jumper between terminal "600 V" and "CON" is for internal
use.
Fire due to overheating resulting from insufficient equipment fan voltage
If the terminals are not reconnected to correspond with the actual line voltage, overheating
and risks to personnel due to smoke and fire may result.
This can also cause the fan fuses to rupture due to overload.
• Set the terminals in accordance with the actual line voltage.
Note
Article numbers for fan fuses
The article numbers for fan fuses that have blown can be found in the spare parts list.
Table 4- 5
72
Setting terminals for the fan transformers (380 to 480 V 3 AC / 500 to 690 V 3 AC)
WARNING
Line voltage assignment for the setting at the fan transformer (3-phase 380 ... 480 V AC)
Line voltage
380 V ± 10 %
400 V ± 10 %
440 V ± 10 %
480 V ± 10 %
Taps of the fan transformer (-G1 -T10, -T1 -T10)
380 V
400 V
440 V
480 V
Operating Instructions, 11/2017, A5E36652151A
Converter cabinet units