Operating area
1: Toolbars
2: Project navigator
3: Workspace
4: Detail view
5.3
Procedure for commissioning with STARTER
Basic procedure using STARTER
STARTER uses a sequence of dialog screens for entering the required drive unit data.
Note
Default settings in dialog screens
These dialog screens contain default settings, which you may have to change according to
your application and configuration.
This is intentional:
Objective: By taking time to consider what configuration data you enter, you can prevent
inconsistencies between the project data and drive unit data (identifiable in online mode).
5.3.1
Creating the project
Click the STARTER icon on the desktop or select the Start > All programs > STARTER >
STARTER menu command in the Windows start menu (e.g., in Windows 7) to start the
STARTER commissioning tool.
The first time you run the software, the main screen (shown below) appears with the
following windows:
● STARTER Getting Started
● STARTER project wizard
The commissioning steps are listed below as a numbered step sequence.
Converter cabinet units
Operating Instructions, 11/2017, A5E36652151A
In this area, you can access frequently used functions via toolbar buttons.
The elements and projects available in the project are displayed here.
In this area, you can change the settings for the drive units.
Detailed information about faults and alarms, for example, is displayed this area.
5.3 Procedure for commissioning with STARTER
Description
Commissioning
197