General converter behavior when in the PROFIenergy energy-saving mode
● When the PROFIenergy energy-saving mode is active, the inverter issues alarm A08800.
● When the PROFIenergy energy-saving mode is active, the inverter does not send any
diagnostic alarms.
● When the PROFIenergy energy-saving mode is active, then the READY-LED flashes
green in the on / off ratio: 500 ms on, 3000 ms off.
● If the bus connection to the control system is interrupted while the inverter is in the
energy-saving mode, the inverter exits the energy-saving mode and resumes normal
operation ("ready_to_operate").
● The inverter changes into normal operation if the control system goes into the stop
condition while the inverter is in the energy-saving mode.
6.9.6.7
Disabling PROFIenergy and pause time
Disabling PROFIenergy
If you set p5611.0 = 1, you disable the response of the converter to PROFIenergy control
commands. In this case, the converter ignores the PROFIenergy control commands.
Pause time
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
– If the pause time is less than p5602[1], the inverter ignores the command.
● Maximum duration: p5606
6.9.6.8
PROFIenergy applications
Applications for PROFIenergy and for programming with SIMATIC S7 are available at the
following link: PROFIenergy applications
(http://support.automation.siemens.com/WW/view/en/20229805/136000&cspltfrm=12&cssw=
0&csbinh=0).
Converter cabinet units
Operating Instructions, 11/2017, A5E36652151A
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
6.9 Communication via PROFINET IO
Operation
373