Siemens SINAMICS S150 NEMA Operating Instructions Manual page 112

Converter cabinet units 15hp-1250hp
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Electrical installation
4.9 Additional connections
4.9.1
Infeed module rated one level lower (option L04)
Description
With this option, an infeed (Active Line Module / Active Interface Module) rated one power
level lower than the Motor Module (inverter) is used.
The option is suitable for the following applications, for example:
● If the Motor Module is operated with pulse frequencies greater than the rated pulse
frequencies, thereby reducing the output power (current derating as a function of the
pulse frequency).
● If the rated power is required in regenerative mode and the system losses are covered by
the Motor Module.
● With motors that have a higher efficiency and/or a lower power factor compared to typical
standard induction motors.
● The maximum current of the Motor Module is required below the maximum power of the
unit, e.g. drives that have a high breakaway torque.
Availability
Option L04 is available for the following cabinet units:
Voltage [V]
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
Constraint
Since the infeed is the element that limits the output power achievable when Option L04 is
used, the following constraints must be observed:
● The rated output current of the Motor Module is available only as long as the infeed
(Active Line Module) is not loaded at rated power.
● The output power is reduced proportional to the line voltage in the event of line supply
undervoltage.
● The unit should be operated with a line power factor cos φ = 1 and should only provide
the active power. An additional compensation of reactive line power is not expedient. This
operating mode with cos φ = 1 corresponds to the factory setting.
110
Article no.
6SL3710-7LE33-1AU3
6SL3710-7LE35-0AU3
6SL3710-7LE36-1AU3
6SL3710-7LE37-5AU3
6SL3710-7LE41-0AU3
Unit rating
Rated output current
[HP / kW]
[A]
250 / 160
310
400 / 250
490
500 / 315
605
600 / 400
745
800 / 560
985
Operating Instructions, 11/2017, A5E36652151A