Electrical installation
4.9 Additional connections
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter if a motor is not connected
dv/dt filters which are operated without a motor being connected can be damaged or
destroyed.
• Never operate a dv/dt filter connected to the Motor Module without a connected motor.
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the relevant maximum pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used.
When so doing, take into account the "Current derating as a function of the pulse frequency;
see Technical data.
Table 4- 31
Max. pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 2 kHz
Article no.
6SL3710-...
7LE32-1AU3
7LE32-6AU3
7LE33-1AU3
7LE33-8AU3
7LE35-0AU3
116
Unit rating
Output current for a
[HP / kW]
pulse frequency of 2 kHz [A]
Supply voltage 3-phase 380 ... 480 V AC
150 / 110
200 / 132
250 / 160
300 / 200
400 / 250
Max. pulse frequency when a dv/dt filter
plus Voltage Peak Limiter is used
210
260
310
380
490
Operating Instructions, 11/2017, A5E36652151A
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz