Electrical installation
4.9 Additional connections
4.9.18.2
Connection
X520: Encoder connection
Table 4- 53
Connector type: 25-pin SUB D connector (pins)
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
1)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
154
Encoder connection X520
Pin
Signal name
1
Reserved, do not use
2
Reserved, do not use
3
S2
4
S4
5
Ground
6
S1
7
S3
8
Ground
9
R1
10
Reserved, do not use
11
R2
12
Reserved, do not use
13
+ Temp
1)
14
Reserved, do not use
15
Reserved, do not use
16
Reserved, do not use
17
Reserved, do not use
18
Reserved, do not use
19
Reserved, do not use
20
Reserved, do not use
21
Reserved, do not use
22
Reserved, do not use
23
Reserved, do not use
24
Ground
25
- Temp
1)
Technical data
Resolver signal A (sin+)
Inverted resolver signal A (sin-)
Ground (for internal shield)
Resolver signal B (cos+)
Inverted resolver signal B (cos-)
Ground (for internal shield)
Resolver excitation positive
Resolver excitation negative
Temperature sensor KTY84-1C130 /
PT1000 / PTC
Ground (for internal shield)
Temperature sensor KTY84-1C130 /
PT1000 / PTC
Converter cabinet units
Operating Instructions, 11/2017, A5E36652151A