Commissioning
5.5 Initial commissioning with the AOP30
Note
Selecting the motor type
The selection of the motor type pre-assigns specific motor parameters and optimizes the
operating characteristics and behavior. Details are described in the List Manual in the p0300
parameter.
Note
Selection of a list motor (p0300 ≥ 100)
When a motor type ≥ 100 is selected, the article number of the associated motor can be
selected via drop-down list.
Note
Commissioning an induction motor
The steps described below also apply to commissioning an induction motor.
When commissioning a permanent-magnet synchronous motor (p0300 = 2), there are a few
special conditions that apply, which are detailed in a separate chapter (see "Setpoint
channel and closed-loop control/Permanent-magnet synchronous motors").
Basic commissioning: entering the encoder data (if available)
248
When the SMC10/SMC20/SMC30 is
connected for encoder evaluation (with
options K46, K48, and K50), it is recognized
by the AOP30 and a screen is displayed in
which you can enter the encoder data.
Navigate within the selection fields with <F2>
and <F3>.
Activate your selection with <F5>.
Operating Instructions, 11/2017, A5E36652151A