Electrical installation
4.9 Additional connections
X150 P1/P2 PROFINET interface
Table 4- 70
Connector type: RJ45 socket
Cable type: PROFINET
Note
Connection cables
The PROFINET interfaces support Auto MDI(X). It is therefore possible to use both crossed
and uncrossed cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are each equipped with a green and
a yellow LED. These LEDs indicate the following status information:
Table 4- 71
LED
Link port
Activity port
T0, T1, T2: Measuring socket contacts
Table 4- 72
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, order number: 1893708
190
X150 P1 and X150 P2 PROFINET
Pin
1
RXP
2
RXN
3
TXP
4
Reserved, do not use
5
Reserved, do not use
6
TXN
7
Reserved, do not use
8
Reserved, do not use
LED states of the X150 P1/P2 PROFINET interface
Color
Status
-
Off
Green
Continuous light
-
Off
Yellow
Flashing light
Measuring socket contacts T0, T1, T2
Socket
M
Ground
T0
Measuring socket contact 0
T1
Measuring socket contact 1
T2
Measuring socket contact 2
Signal name
Description
Missing or faulty link
10 or 100 Mbit link available
No activity
Data is being received or sent at port x
Function
Voltage: 0... 5 V
Resolution: 8 bits
Load current: max. 3 mA
Sustained short-circuit-proof
The reference potential is terminal M
Operating Instructions, 11/2017, A5E36652151A
Technical specifications
Receive data +
Receive data -
Send data +
Send data -
Technical specifications
Converter cabinet units