0x7C
Parameter %s [%s]: write access only
in the commissioning state, device
download (device: p0009 = 29).
0x7D
Parameter %s [%s]: write access only
in the commissioning state, device
parameter reset
(device: p0009 = 30).
0x7E
Parameter %s [%s]: write access only
in the commissioning state, device
ready (device: p0009 = 0).
0x7F
Parameter %s [%s]: write access only
in the commissioning state, device
(device: p0009 not equal to 0).
0x81
Parameter %s [%s] must not be
written during download.
0x82
Transfer of master control is blocked
by BI: p0806.
0x83
Parameter %s [%s]: requested BICO
interconnection not possible.
0x84
Parameter %s [%s]: parameter
change inhibited (refer to p0300,
p0400, p0922)
0x85
Parameter %s [%s]: access method
not defined.
0x87
Write job will not be executed.
0xC8
Below currently valid limit.
0xC9
Above currently valid limit.
0xCC
Write access not permitted.
Converter cabinet units
Operating Instructions, 11/2017, A5E36652151A
6.7 Communication according to PROFIdrive
Comments
BICO output does not supply float values. The BICO input,
however, requires a float value.
The write job is rejected because know-how protection is
active.
Modification request for a value that, although within
"absolute" limits, is below the currently valid lower limit.
Modification request for a value that, although within
"absolute" limits, is above the currently valid upper limit
(e.g., governed by the current converter rating).
Write access is not permitted because an access key is
not available.