Settings and Measurement
Logic ................................... Color
3-16
• EU (Engineering Unit Settings):
This menu is used to scale the measured values and convert them to
other units.
Meas. Value: Specifies the numeric value to be converted.
EU Value:
Specifies output after conversion.
Unit:
Specifies the converted unit. The unit can be specified
as a user-defined character string consisting of
alphanumerics. It can also be specified by using the
Select setting to select a unit.
Select:
Selects the type of engineering unit.
Choose:
Selects the converted unit. The unit displayed here is
the unit for the type of engineering unit selected by the
Select setting.
• Slope: Sets the condition for the input signal operation.
H : Operates when the signal is a rising signal.
L : Operates when the signal is a falling signal.
• Color specification for each channel:
This parameter enables the display colors for each channel to be
changed.
• Filter: Set the filter to On when there is likely to be noise in the input.
Off: Disables the filter
On: Enables the filter