Commissioning (basic settings)
Information
9.5.

Test run

9.5.1.

Direction of rotation at mechanical position indicator: check

Information
66
SA 25.1
SA 48.1/SAR 25.1
Parameter MD2 slave address is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
Only perform test run only once all settings previously described have been
performed.
The direction of rotation can be checked at the position indicator if available. (Chapter
<Direction of rotation at mechanical position indicator: check>)
The direction of rotation must be checked at the hollow shaft/stem if no mechanical
position indicator is available. (Chapter <Direction of rotation at hollow shaft/stem:
check>)
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
Switch off before reaching the end position.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.