12.2.
Maintenance
Lubrication
12.3.
Disposal and recycling
SAR 30.1 Control unit: electronic (MWG)
In the factory, the gear housing is filled with grease.
Grease change is performed during maintenance
-
Generally after 4 to 6 years for modulating duty.
-
Generally after 6 to 8 years if operated frequently (open-close duty).
-
Generally after 10 to 12 years if operated infrequently (open-close duty).
We recommend replacing the seals when changing the grease.
Additional lubrication of the gear housing is not required during operation.
Our devices have a long lifetime. However, they have to be replaced at one point in
time. The devices have a modular design and may, therefore, easily be separated
and sorted according to materials used, i.e.:
electronic scrap
various metals
plastics
greases and oils
The following generally applies:
Greases and oils are hazardous to water and must not be released into the
environment.
Arrange for controlled waste disposal of the disassembled material or for sep-
arate recycling according to materials.
Observe the national regulations for waste disposal.