Motor Connection; Motor Connection Compartment: Open; Motor Cables: Connect - AUMA SA 25.1 Operating Instructions Manual

Multi-turn actuators, control unit: electronic mwg with actuator controls, non-intrusive
Hide thumbs Also See for SA 25.1:
Table of Contents

Advertisement

Electrical connection
5.3.1.

Motor connection

5.3.1.1. Motor connection compartment: open

5.3.1.2. Motor cables: connect

34
SA 25.1
SA 48.1/SAR 25.1
Figure 33: Motor connection compartment: open
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Cable gland
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
2.
Insert cable gland suitable for connecting cable.
The enclosure protection IP... stated on the name plate is only ensured if suit-
able cable glands are used.
Figure 34: Name plate, example with enclosure protection IP68
Table 19:
Terminal cross sections and terminal tightening torques
Type
Speed
SA 25.1
4
22
SAR 25.1
32
90
SA 30.1
4
22
SAR 30.1
32
45
63
90
SA 35.1
4
5.6
8
22
32
45
SAR 30.1 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Modbus RTU
Terminal cross sections
2
0.5
16 mm
2
2.5
35 mm
2
4
16 mm
2
10
35 mm
2
16
70 mm
2
4
16 mm
2
10
35 mm
2
16
70 mm
Tightening torques
2.0 Nm
3.5 Nm
1.2
2.4 Nm
4.0
5.0 Nm
6.0
12 Nm
1.2
2.4 Nm
4.0
5.0 Nm
6.0
12 Nm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sa 48.1Sar 25.1Sar 30.1Ac 01.2

Table of Contents